IDENTIFYING THE UNKNOWN CIRCUIT-BREAKER STATUSES IN POWER NETWORKS

被引:67
作者
ABUR, A
KIM, H
CELIK, MK
机构
[1] Department of Electrical Engineering, Texas A&M University, College Station
[2] Consulting Engineer, San Francisco
关键词
TOPOLOGY ERRORS; IDENTIFICATION; STATE ESTIMATION; WEIGHTED LEAST ABSOLUTE VALUE; LINEAR PROGRAMMING;
D O I
10.1109/59.476072
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper describes an approach by which the circuit breaker status errors can be detected and identified-in the presence of analog measurement errors. This is accomplished by using the least absolute value (LAV) state estimation method and applying the previously suggested two stage estimation approach in [15]. The ability of the LAV estimators to reject inconsistent measurements, is exploited in order to differentiate between circuit breaker status and analog measurement errors. The first stage of estimation uses a bus level network model as in conventional LAV estimators. Results of Stage 1 are used to draw a set of suspect buses whose substation configurations may be erroneous. In the second stage, the identified buses are modeled in detail using the bus sections and the circuit breaker models while keeping the bus level network models for the rest of the system. The LAV estimation is repeated for the expanded system model and any remaining significant normalized residuals are flagged as bad analog measurements, while the correct topology is determined based on the estimated flows through the modeled circuit breakers in the substations. The proposed approach is implemented and tested. Simulation results for cases involving circuit breaker status and/or analog measurement errors are provided.
引用
收藏
页码:2029 / 2037
页数:9
相关论文
共 21 条
[1]   A BAD DATA IDENTIFICATION METHOD FOR LINEAR-PROGRAMMING STATE ESTIMATION [J].
ABUR, A .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1990, 5 (03) :894-901
[2]   A FAST ALGORITHM FOR THE WEIGHTED LEAST ABSOLUTE VALUE STATE ESTIMATION [J].
ABUR, A ;
CELIK, MK .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1991, 6 (01) :1-8
[3]   IMPROVED ALGORITHM FOR DISCRETE L1 LINEAR-APPROXIMATION [J].
BARRODALE, I ;
ROBERTS, FDK .
SIAM JOURNAL ON NUMERICAL ANALYSIS, 1973, 10 (05) :839-848
[4]   POWER SYSTEM STATE ESTIMATION RESIDUAL ANALYSIS - AN ALGORITHM USING NETWORK TOPOLOGY [J].
CLEMENTS, KA ;
KRUMPHOLZ, GR ;
DAVIS, PW .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1981, 100 (04) :1779-1787
[5]  
CLEMENTS KA, 1988, WIN IEEE M
[6]  
CLEWER BC, 1988, IFAC S POWER SYSTEMS
[7]  
COSTA AS, 1993, WIN IEEE M
[8]   BAD DATA-ANALYSIS FOR POWER-SYSTEM STATE ESTIMATION [J].
HANDSCHIN, E ;
SCHWEPPE, FC ;
KOHLAS, J ;
FIECHTER, A .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1975, PA94 (02) :329-337
[9]   SUBSTATION DATA VALIDATION [J].
IRVING, MR ;
STERLING, MJH .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1982, 129 (03) :119-122
[10]  
KOGLIN HJ, 11TH P PSCC, V1, P633