THE UTILITY REQUIREMENTS FOR A DISTRIBUTION FAULT CURRENT LIMITER

被引:81
作者
SLADE, PG
WU, JL
STACEY, EJ
STUBLER, WF
VOSHALL, RE
BONK, JJ
PORTER, J
HONG, L
DICK, EP
机构
[1] GANNON UNIV,ELECT ENGN,ERIE,PA 16541
[2] ELECT POWER RES INST,WASHINGTON,DC 20036
[3] CONSOLIDATED EDISON CO NEW YORK INC,NEW YORK,NY 10003
[4] ONTARIO HYDRO,TORONTO,ONTARIO,CANADA
关键词
D O I
10.1109/61.127043
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A study is presented that has investigated the need for a distribution current limiting device (DCLD) by the utility industry. The study also has evaluated what specifications would be acceptable and what DCLD technique would supply the utilities' needs. Using this survey and a distribution system analysis, a DCLD that could limit a 20 kA fault to 10 kA in a 15 kV circuit was shown to be the primary candidate for further development. The study showed that gate turn-off thyristors (GTO) are the best state-of-the-art technology available that could be developed into a practical DCLD. A recommendation was made to develop a DCLD using GTOs.