COMPARING ALUMINUM AND IRON COAGULANTS FOR IN-LINE FILTRATION OF COLD WATER

被引:31
作者
HAARHOFF, J
CLEASBY, JL
机构
来源
JOURNAL AMERICAN WATER WORKS ASSOCIATION | 1988年 / 80卷 / 04期
关键词
IRON COMPOUNDS - Efficiency - WATER FILTRATION - Temperature Control;
D O I
10.1002/j.1551-8833.1988.tb03022.x
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Pilot studies showed that with water temperatures less than 37 degree F (3 degree C) and raw water turbidities less than 2 ntu, ferric chloride removed turbidity more efficiently than did aluminum sulfate but that aluminum sulfate caused slower head loss development. The total clogging head loss at the onset of turbidity breakthrough, however, was approximately the same for both coagulants. Equivalent head loss development and turbidity removal were demonstrated at a molar iron-to-aluminum dosage ratio of 3:5. 6.