FIELD-TEST RESULTS FOR A MULTISHOT 12.47 KV FAULT CURRENT LIMITER

被引:13
作者
ENGELMAN, N [1 ]
SCHREURS, E [1 ]
DRUGGE, B [1 ]
机构
[1] ABB CORP RES,VASTERAS,SWEDEN
关键词
FAULT CURRENT LIMITER; CURRENT LIMITING; SWITCHGEAR; LIMITERS; POWER DISTRIBUTION NETWORKS;
D O I
10.1109/61.85851
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
During ten months of 1989, a prototype multishot 12.47 kV fault current limiter (FCL) was installed in a field test mode at a substation in Lincoln, Nebraska. This paper presents the principles of operation, computer simulations and the results of the field test. Nineteen fault occurrences were successfully handled by the FCL. Examples of actual faults include currents of 3900 A reduced to 2140 A and bus voltage sags improved from .33 to .9 per unit. The field tests established that a fault current limiter utilizing this technology is ready for utilization on 15 kV class distribution circuits.
引用
收藏
页码:1081 / 1087
页数:7
相关论文
共 6 条
[1]  
GLENN D, 1985, IEEE T IND APPLICATI, V21
[2]  
KEDERS T, 1976, JUL IEEE PES SUMM M
[3]  
NAKAYAMA H, 1989, IEEE T POWER DELIVER, V4
[4]  
PFLANZ HM, 1981, IEEE T POWER APPARAT, V100
[5]  
THANAWALA HL, 1970, ENERGY INT, V7
[6]  
1989, BASIC CONCEPTS ASS T