ANALYSIS OF DC ARC FURNACE OPERATION AND FLICKER CAUSED BY 187 HZ VOLTAGE DISTORTION

被引:27
作者
TANG, L
MUELLER, D
HALL, D
SAMOTYJ, M
RANDOLPH, J
机构
[1] WISCONSIN ELECT POWER CO,MILWAUKEE,WI
[2] CHARTER STEEL,ELECT & CONTROLS PROJECTS,SAUKVILLE,WI
[3] ELECT POWER RES INST,DIV CUSTOMER SYST,POWER ELECTR & CONTROLS PROGRAM,PALO ALTO,CA 94303
关键词
VOLTAGE FLICKER; DC ARC FURNACES; CONVERTERS; HARMONICS; POWER QUALITY; INTERHARMONICS; EMTP;
D O I
10.1109/61.296295
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper analyzes an unusual flicker-like disturbance during the operation of a DC arc furnace. A harmonic resonance, excited by an excessive amount of uncharacteristic converter current harmonics, was the main cause of the disturbance. A study was performed in which the phenomenon was duplicated with the Electro-magnetic Transients Program. The simulation model and results are described. The generation of uncharacteristic converter current harmonics under normal and abnormal converter operation are demonstrated. The significant conditions leading to the unusual 187 Hz disturbance and flicker complaints are discussed.
引用
收藏
页码:1098 / &
相关论文
共 14 条
[1]   ARC FURNACE FLICKER MEASUREMENTS AND CONTROL [J].
BHARGAVA, B ;
WILHELM, MR .
IEEE TRANSACTIONS ON POWER DELIVERY, 1993, 8 (01) :400-410
[2]  
DAVYDOV V, ELECTROTECH 92 P, P30
[3]  
GUNTHER E, RESONANT, V1, P3
[4]  
HING DJC, 1982, IEEE T POWER AP SYST, V101, P2982, DOI 10.1109/TPAS.1982.317627
[5]  
KIMBARK, 1971, DIRECT CURRENT TRANS, V1, P318
[6]  
KUBOTA T, ELECTROTECH 92 P, P1
[7]  
MIYASHITA T, ELECTROTECH 92 P, P11
[8]  
NISHIDAI J, ELECTROTECH 92 P, P896
[9]  
SAITO, ELECTROTECH 92 P, P852
[10]  
SCHWABE WE, 1986, AISE T, V63, P230