HIGH IMPEDANCE FAULT ARCING ON SANDY SOIL IN 15KV DISTRIBUTION FEEDERS - CONTRIBUTIONS TO THE EVALUATION OF THE LOW-FREQUENCY SPECTRUM

被引:195
作者
EMANUEL, AE [1 ]
CYGANSKI, D [1 ]
ORR, JA [1 ]
SHILLER, S [1 ]
GULACHENSKI, EM [1 ]
机构
[1] NEW ENGLAND POWER SERV CORP,WESTBOROUGH,MA 01581
关键词
Arcing; Harmonics; System Protection;
D O I
10.1109/61.53070
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents the measured values of current harmonics at a staged high impedance ground fault on sandy soil. The measured low frequency spectrum is compared with current harmonics recorded continuosly for one week at the substation. This comparison was carried out to determine to what extent 120 Hz and 180 Hz components may be used to help detect a high impedance fault. The field measurements are supported by a simple theoretical model and laboratory measurements. It is concluded that for the studied feeder detection of high impedance arcing faults may be possible by monitoring of the second harmonic current. © 1990 IEEE