HEAT-TRANSFER COEFFICIENT DURING 2-PHASE FLOW BOILING OF HFC-134A

被引:28
作者
HAMBRAEUS, K
机构
[1] Royal Institute of Technology, Department of Applied Thermodynamics and Refrigeration
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 1991年 / 14卷 / 06期
关键词
HEAT TRANSFER; 2-PHASE FLOW; ALTERNATIVE REFRIGERANTS;
D O I
10.1016/0140-7007(91)90033-D
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper reports a study of the evaporation of HFC-134a inside smooth, horizontal tubes. Tests were performed with the pure refrigerant and with oil-refrigerant mixtures. The heat flux was varied from 2 to 10 kW m-2. The inner diameter of the tubes was 12 mm. Two evaporators were used, 4 and 10 m long, and the oil content was varied from 0 to 2.5 mass percentage (synthetic oil, EXP-0275). Oil-free HFC-134a had a higher heat transfer coefficient than HCFC-22 at the same heat and mass fluxes. The effect of oil in the refrigerant is dependent on the heat flux. At 2 and 4 kW m-2 the heat transfer coefficient had a maximum value for an oil content of around 0.5 mass percentage; no increase is registered for a heat flux of 6 k W m-2. The heat transfer coefficients for the pure refrigerant were also compared with two existing correlations. The measured heat transfer coefficients averaged over the evaporator deviate less than 40% from the correlation according to Pierre. The heat transfer coefficients at the short evaporator lie within 20%. The correlation given by Jung overestimates the heat transfer coefficient by approximately 50%.
引用
收藏
页码:357 / 362
页数:6
相关论文
共 10 条
[1]  
Spauschus, HFC 134a as a substitute refrigerant for CFC 12, Proceedings of Meetings of IIR Commissions B1, B2, E1 and E2, pp. 397-400, (1988)
[2]  
Pierre, Värmeövergången vid kokande köldmedier i horisontella rör, Kylteknisk tidkr., (1957)
[3]  
Pierre, Värmeövergång vid kokande köldmedier i horisontella rör, Kylteknisk tidskr., (1969)
[4]  
Chen, Correlation for boiling heat transfer to saturated fluids in convective flow, I&EC Proc Des Dev, 5, pp. 322-329, (1966)
[5]  
Jung, McLinden, Radermacher, Didron, Horizontal flow boiling heat transfer experiments with a mixture of R22/R114, Int J Heat Mass Transfer, 32, pp. 131-145, (1989)
[6]  
Jaeger, Empirische methoden zur vorausberechnung thermodynamischer eigenschaften von öl-kältemittel-gemischen, Kältetech-Klimat, 24, pp. 35-52, (1973)
[7]  
Schlager, Pate, Bergles, A survey of refrigerant heat transfer and pressure drop emphasizing oil effects and in-tube augmentation, ASHRAE Trans, 93, pp. 392-416, (1987)
[8]  
Wilson, Basu, Thermodynamic properties of a new strato-spherically safe working fluid-Refrigerant 134a, ASHRAE Trans, 94, pp. 2095-2104, (1988)
[9]  
ICI Chemicals & Polymers, Arcton 134a Preliminary Data Sheet, (1988)
[10]  
ASHRAE Handbook, Fundamentals, (1981)