DESIGN AND INSTALLATION OF 500-KV BACK-TO-BACK SHUNT CAPACITOR BANKS

被引:10
作者
FURUMASU, BC [1 ]
HASIBAR, RM [1 ]
ENSIGN, RL [1 ]
BHARGAVA, B [1 ]
HARDER, JE [1 ]
机构
[1] ABB POWER,T&D CO,BLOOMINGTON,IN
关键词
SHUNT CAPACITORS; BACK TO BACK SWITCHING; CURRENT LIMITING REACTORS; INRUSH CURRENT; TRANSIENT STABILITY CONTROL;
D O I
10.1109/61.127046
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper describes Bonneville Power Administration's first 500-kV back-to-back shunt capacitor installation. The primary purpose of the capacitor banks is to support AC system voltage for transient stability following an outage of the HVDC Intertie line between Oregon and Southern California. Design studies and equipment requirements are detailed herein in addition to Electromagnetic Transients Program (EMTP) studies and subsequent field test results. Current-limiting reactors are used to limit inrush and outrush currents during capacitor switching. It is believed that this is the first 500-kV back-to-back capacitor installation in the United States.