REDUCTION OF VOLTAGE FLICKER OF A SIMULATED ARC FURNACE BY REACTIVE COMPENSATION

被引:8
作者
OKELLY, D
SALEM, HH
SINGH, B
机构
[1] Department of Electrical Engineering, University of Bradford, Bradford
关键词
D O I
10.1016/0378-7796(92)90081-B
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The paper describes a single-phase laboratory model of an arc furnace with fast acting reactive compensation by a thyristor controlled shunt reactor to reduce system voltage variations. Sampled values of load current are processed by a microprocessor based system to obtain the fundamental reactive component which is then used as a control parameter for the compensator. Results for a step change of load illustrate the fast response. Voltage flicker with low frequency amplitude-modulated load changes is significantly reduced.
引用
收藏
页码:135 / 139
页数:5
相关论文
共 7 条
[1]  
Swinden, The Arc Furnace, (1980)
[2]  
Dixon, Kendall, Supply to arc furnaces measurements and prediction of supply—voltage fluctuations, Proceedings of the Institution of Electrical Engineers, 119, pp. 456-465, (1972)
[3]  
Dixon, Friedlander, Seddon, Young, Static shunt compensators for voltage flicker suppression, IEE Conf. Publ. London, No. 8, pp. 45-61, (1964)
[4]  
O'Kelly, Abu El Nour, Computation of static reactor performance, IEEE PES Winter Meeting, New York, USA, 1978, (1978)
[5]  
Frank, Ivner, TYCAP, power factor correction equipment using thyristor-controlled capacitors for arc furnaces, ASEA J., 46, pp. 147-152, (1973)
[6]  
Hosano, Yano, Takeda, Yuga, Sueda, Suppression and measurement of arc furnace flicker with a large static VAR compensation, IEEE Trans., 98 PAS, pp. 2276-2284, (1979)
[7]  
Ashmole, Cornfield, Design and use of a digital meter for monitoring system voltage flicker and harmonics, IEE Conf. Publ., London, No. 210, pp. 160-165, (1982)