MANHOLE EXPLOSIONS DUE TO ARCING FAULTS ON UNDERGROUND SECONDARY DISTRIBUTION CABLES IN DUCTS

被引:23
作者
KOCH, B
CARPENTIER, Y
LIPSKI, T
BHANGU, JP
BRUNING, AM
KROPP, C
机构
[1] HYDRO QUEBEC,MONTREAL H2P 1S7,QUEBEC,CANADA
[2] GDANSK TECH UNIV,PL-80952 GDANSK,POLAND
[3] LECTROMECH DESIGN CO,HERNDON,VA 22071
[4] OTTAWA HYDRO,OTTAWA,ONTARIO,CANADA
关键词
ARCING FAULT; SECONDARY DISTRIBUTION; UNDERGROUND DISTRIBUTION; MANHOLE EXPLOSION;
D O I
10.1109/61.141861
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Arcing faults on low-voltage insulated conductors are widely considered to be self-extinguishing and consequently not very hazardous to people or property. Nevertheless, a number of arcing faults recently occurred on Hydro-Quebec's underground secondary 120/240-V and 347/600-V systems and caused manhole explosions in downtown Montreal. To trace the probable cause, a series of staged tests was performed in IREQ's high-power laboratory. The results obtained prove that in wet, dirty ducts an arcing fault can take the form of an interrupted arc which is difficult if not impossible for common overcurrent protections systems to detect. However, any such fault that has a long duration produces a significant amount of gaseous by-products which escape to the ends of the duct where they can ignite or form explosive concentrations.
引用
收藏
页码:1425 / 1433
页数:9