SVC PLACEMENT USING CRITICAL MODES OF VOLTAGE INSTABILITY

被引:101
作者
MANSOUR, Y
XU, WS
ALVARADO, F
RINZN, CHW
机构
[1] UNIV WISCONSIN,MADISON,WI 53706
[2] ROYAL GOVT BHUTAN,DEPT POWER,THIMPHY,BHUTAN
关键词
D O I
10.1109/59.317664
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The location of SVC (Static VAR Compensators) and other types of shunt compensation devices for voltage support is an important practical question. This paper considers a tool based on the determination of critical modes. Critical modes are computed by studying the system modes in the vicinity of the Point of Collapse. System participation factors for the critical mode are used to determine the most suitable sites for system reinforcement. Because the method does not rely on base case linearizations, the method is able to properly consider all system limits and nonlinear effects. The paper tests the proposed method by performing an assessment of the impact of the addition of Static VAR compensators to a 1380 bus model of the BC Hydro system.
引用
收藏
页码:757 / 763
页数:7
相关论文
共 16 条
[1]  
AJJARAPU V, 1991, MAY IEEE POW IND COM, P304
[2]  
ALVARADO FL, 1991, APR NSF WORKSH IMP L, P53
[3]  
ALVARADO FL, 1988, SEP P INT C BULK POW
[4]  
ALVARADO FL, 1993, COMPUTATIN CLOSEST B
[5]  
CANIZARES C, 1992, JAN IEEE PES WINT M
[6]  
CHHEWANG R, 1992, 24TH N AM POW S
[7]   OBSERVATIONS ON THE GEOMETRY OF SADDLE NODE BIFURCATION AND VOLTAGE COLLAPSE IN ELECTRICAL-POWER SYSTEMS [J].
DOBSON, I .
IEEE TRANSACTIONS ON CIRCUITS AND SYSTEMS I-FUNDAMENTAL THEORY AND APPLICATIONS, 1992, 39 (03) :240-243
[8]  
ELWOOD DM, PNL7632 BAT PAC NW L
[9]  
Gao B., 1992, IEEE T POWER SYSTEMS, V7
[10]  
HILL DJ, 1992, IN PRESS IEEE T POWE