PREDICTIONS OF MOISTURE REMOVAL EFFICIENCIES FOR PACKED-BED DEHUMIDIFICATION SYSTEMS

被引:84
作者
CHUNG, TW
机构
[1] Energy and Resources Laboratories, Industrial Technology Research Institute, Hsinchu
来源
GAS SEPARATION & PURIFICATION | 1994年 / 8卷 / 04期
关键词
LIQUID DESICCANT; DEHUMIDIFICATION; COLUMN EFFICIENCY; WATER VAPOR;
D O I
10.1016/0950-4214(94)80007-3
中图分类号
TQ [化学工业];
学科分类号
0817 ;
摘要
Liquid desiccant-based dehumidification systems have been widely used to remove water vapour from air in a packed column using different liquid desiccants. The liquid desiccants are usually grouped into two categories: aqueous solutions of inorganic salts and aqueous solutions of organic compounds. In order to design such a desiccant-dehumidification system, correlations of the column performance parameters are necessary. A correlation of column efficiency for different packings and desiccant solutions was developed in this study using lithium chloride (LiCl) as the inorganic salt and triethylene glycol (TEG) as the organic compound. This correlation involves the air and liquid flow rates, air and liquid inlet temperatures, column and packing dimensions, and the equilibrium properties of the desiccant solutions. The correlation was tested for polypropylene Flexi rings, ceramic Berl saddles, glass Raschig rings and polypropylene Pall rings. The average value of the errors between predicted values and experimental data was about 7%.
引用
收藏
页码:265 / 268
页数:4
相关论文
共 9 条
[1]  
Bravo J.L., 1986, HYDROCARB PROCESS, P45
[2]  
BRAVO JL, 1985, HYDROCARB PROCESS, V64, P91
[3]  
CHUNG TW, 1992, SEP INT S DIST ABS B
[4]  
CHUNG TW, 1991, 7TH S SEP SCI TECHN
[5]   NANOFILTRATION EXTENDS THE RANGE OF MEMBRANE FILTRATION [J].
ERIKSSON, P .
ENVIRONMENTAL PROGRESS, 1988, 7 (01) :58-62
[6]   CALCULATION OF HEAT AND MASS-TRANSFER COEFFICIENTS IN A PACKED TOWER OPERATING WITH A DESICCANT-AIR CONTACT SYSTEM [J].
GANDHIDASAN, P ;
KETTLEBOROUGH, CF ;
ULLAH, MR .
JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME, 1986, 108 (02) :123-128
[7]  
Hines A. L, 1985, MASS TRANSFER FUNDAM
[8]  
SCALABRIN G, 1984, TERMOTECNICA, V38, P65
[9]   EFFECTIVENESS OF MOISTURE REMOVAL FOR AN ADIABATIC COUNTERFLOW PACKED TOWER ABSORBER OPERATING WITH CACL2-AIR CONTACT SYSTEM [J].
ULLAH, MR ;
KETTLEBOROUGH, CF ;
GANDHIDASAN, P .
JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME, 1988, 110 (02) :98-101