AN ALGORITHM FOR IMPROVING THE RELIABILITY OF DETECTION WITH PROCESSING OF MULTIPLE SENSORS SIGNAL

被引:12
作者
ISHII, H
ONO, T
YAMAUCHI, Y
OHTANI, S
机构
[1] Department of Electrical Engineering, College of Science and Technology, Nihon University, 101, 1-8 Kanda Surugadai, Chiyoda-ku Tokyo
[2] R and D Center, Hochiki Corporation, Machida-shi, Tokyo, 194
关键词
D O I
10.1016/0379-7112(91)90048-4
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Recent surveys show that most of the false alarms of fire alarm systems are given by deceptive phenomena caused by human actions, such as cigarette smoking and cooking. Software-controlled systems have a potential ability in increasing the reliability of detection signals by data processing. However, it is rather difficult to distinguish an early stage fire from those deceptive phenomena only by processing the data of a single sensor. The authors' new algorithm utilizes the signals from three different sensors, i.e. temperature, smoke and gas (CO) concentration. Incorporating a mathematical fire model, these signals are translated into source parameters such as heat release rate, and smoke and gas generation rates. The conditions of the fire are then analyzed using the cross-correlation function between these source parameters. Testing the algorithm has been done using some experimental data and a promising result has been obtained.
引用
收藏
页码:469 / 484
页数:16
相关论文
共 14 条
[1]  
Takeuchi, Ishii, Intelligent systems: Present designs, what they are and what they might achieve, Int. Fire Security & Safety Exhbn & Conf., (1985)
[2]  
Ono, Ishii, Muroi, Frequency response required for an intelligent alarm system, Bull. Japanese Assoc. Fire Sci. & Engng, 35, 2, pp. 23-30, (1986)
[3]  
Ono, Ishii, Muroi, An algorithm for fire judgement in early stage, Trans. Soc. Instr. & Control Eng., 22, pp. 1290-1297, (1986)
[4]  
Ono, Ishii, Muroi, Multi-dimensional measurement of early stage fire, Trans. Soc. Instr. & Control Eng., 24, pp. 794-801, (1988)
[5]  
Kawagoe, Fire behavior in rooms, Report of the Building Research Inst. (Japan), (1958)
[6]  
Rockett, Fire induced flow in an enclosure, Combustion Science and Technology, 12, pp. 165-175, (1976)
[7]  
Quintiere, Growth of fire in building compartments, Fire Standard and Safety, ASTM STP 614, (1977)
[8]  
Mitler, Emmons, Documentation for CFC V, 5th Harvard computer fire code, NBS-GCR 81-344, (1981)
[9]  
Zukoski, Development of a stratified ceiling layer in the early stages of a closed-room fire, Fire and Materials, 2, pp. 54-61, (1978)
[10]  
Cooper, A mathematical model for estimating available safe egress time in fires, Fire and Materials, 3, pp. 135-144, (1982)