10-MW GTO CONVERTER FOR BATTERY PEAKING SERVICE

被引:105
作者
WALKER, LH
机构
[1] Drive Development Engineering, Drive Systems Department, General Electric Company, Salem, VA 24153, 1501 Roanoke Boulevard
关键词
D O I
10.1109/28.52675
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
A bidirectional 18-pulse voltage source converter utilizing gate turn-off thyristors (GTO's) is described. The converter, which is rated 10 MVA, was placed in service in early 1988 to connect an energy storage battery to a utility grid. The converter is rated and controlled to operate in all four quadrants (discharge, charge, leading vars, or lagging vars) at the full 10-MVA rating. It is capable of independent rapid control of real and reactive power with a transient response of 16 ms to changes in commanded value of real or reactive power. Thus it is usable as a reactive power controller (static var control), voltage control, frequency control, power system stabilizer, or as a real power peaking station. For use as a reactive power controller only, no battery would be needed. The design, construction, control, and application of the converter are described, and performance data taken at factory power test and at the installation are given. © 1990 IEEE
引用
收藏
页码:63 / 72
页数:10