ENERGY AND ECONOMIC COMPARISONS OF AIR-TO-AIR HEAT-PUMPS AND CONVENTIONAL HEATING-SYSTEMS FOR THE TURKISH CLIMATE

被引:12
作者
KAYGUSUZ, K
机构
[1] Karadeniz Technical University, Department of Chemistry, Trabzon
关键词
D O I
10.1016/0306-2619(93)90035-N
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In order to investigate the energy performance of air-to-air heat Pumps for residential heating in the Black Sea region of Turkey, an experimental set-up was constructed. An electrically driven air-to-air heat pump was used for heating a laboratory building with a floor of 75 m2. The experimental results were obtained for December, January, February, March, April and May of the 1991-2 heating season. The experimentally obtained results are used to calculate the heat pump's coefficient of performance (COP). Actual experimental performance data were used to generate third-order polynomials relating the heat pump's COP to the outdoor air temperature. Also, economic comparisons were made of the heat pump's performance with electrical resistance, oil, gas and coal-fired heating systems, using an annualised life-cycle costing method. This showed that the heat pump offers economic advantages over the oil and coal-fired boiler systems, but is not an economic alternative to the gas-fired heating system. Because the unit price of the gas is 3.84 times less than that for electricity, to become competitive with a gas-fired boiler, either the capital cost of the heat pump must be substantially reduced or its seasonal COP increased by about 60%: it should also be driven by a gas engine rather than an electric engine.
引用
收藏
页码:257 / 267
页数:11
相关论文
共 12 条
[1]  
BITTLE BB, 1983, ASHRAE T, V89, P743
[2]  
CALM JM, 1984, ASHRAE J AUG, P40
[3]  
GOLDSCHMIDT WV, 1982, ASHRAE T, V88, P479
[4]  
IMAIIDA T, 1985, ASHRAE T, V91, P1527
[5]  
KUWAHARA E, 1986, ASHRAE T, V92, P20
[6]  
Matsubara T., 1978, Advances in Animal Electrocardiography, P32
[7]  
MERRIL P, 1981, ASHRAE T, V87, P381
[8]  
MILLER WA, 1984, ASHRAE T, V90, P1009
[9]  
REAY DA, 1979, HEAT PUMPS DESIGN AP, P1
[10]   ENERGY AND ECONOMIC COMPARISONS OF DOMESTIC HEAT-PUMPS AND CONVENTIONAL HEATING-SYSTEMS IN THE BRITISH CLIMATE [J].
TASSOU, SA ;
MARQUAND, CJ ;
WILSON, DR .