A NEW METHOD OF HARMONIC POWER DETECTION BASED ON THE INSTANTANEOUS ACTIVE POWER IN 3-PHASE CIRCUITS

被引:70
作者
TANAKA, T [1 ]
AKAGI, H [1 ]
机构
[1] OKAYAMA UNIV,OKAYAMA 700,JAPAN
关键词
D O I
10.1109/61.473386
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a new method of harmonic power detection based on the instantaneous active power in three-phase circuits, and its applications to search for dominant harmonic sources in power systems. The proposed method requires only band elimination filters and a three-phase active power meter to detect the harmonic active power, and it is able to deal with harmonic power flow more easily and precisely than a conventional one which is based on Fourier series of single-phase circuits. In addition, measurement errors of the harmonic power are discussed theoretically. The validity of the proposed method is demonstrated by digital simulation.
引用
收藏
页码:1737 / 1742
页数:6
相关论文
共 9 条
[1]   INSTANTANEOUS REACTIVE POWER COMPENSATORS COMPRISING SWITCHING DEVICES WITHOUT ENERGY-STORAGE COMPONENTS [J].
AKAGI, H ;
KANAZAWA, Y ;
NABAE, A .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1984, 20 (03) :625-630
[2]  
Inoue M., 1981, IEEJ T POWER ENERGY, V101, P451
[3]  
INOUE M, 1991, IEEJ IAS ANN C
[4]  
KOMATSUGI K, 1986, IEEE PESC C REC, P283
[5]  
MARRAM EB, 1992, IEEE T IND APPL, V28, P782
[6]  
SHIBATA T, 1992, HIOKI REV, V13
[7]  
TROGER R, 1956, ETZ A, P706
[8]  
TROGER R, 1953, ENERGETISCHE DARSTEL, P533
[9]  
COMPONENT PRODUCTS D