INVESTIGATION OF THE PERFORMANCE BEHAVIOR OF A COMPRESSION REFRIGERATING UNIT WITH HALOGEN REFRIGERANT MIXTURES R22/R142B, R22/R114 AND R22/R12

被引:5
作者
TREPP, C
SAVOIE, P
KRAUS, WE
机构
[1] Institut für Verfahrens- und Kältetechnik, ETH Zürich
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 1992年 / 15卷 / 02期
关键词
HALOGEN MIXTURES; COMPRESSION UNITS; ENERGY SAVINGS;
D O I
10.1016/0140-7007(92)90034-R
中图分类号
O414.1 [热力学];
学科分类号
摘要
Several experiments with binary refrigerant mixtures were made to investigate the possibility of replacing R12, which causes environmental problems. The mixture R22/R142b can be recommended as an alternative. A mass fraction range of 50-70% R22 in this mixture was found to be reasonable. The same experiments were used to obtain performance data and to check the potential for saving energy. Several experiments showed that by using temperature effects during phase changes and by designing the plant accordingly energy can be saved. The results indicate that R22/R142b mixtures are good alternatives for industrial use.
引用
收藏
页码:101 / 111
页数:11
相关论文
共 15 条
[1]  
Savoie, Untersuchung des Betriebsverhaltens spezieller Halogenkältemittelgemische an einer Kompressions-wärmepumpe, Diplomarbeit, (1988)
[2]  
Energieeinsparung durch Mehrstoffkälteanlagen, Schriftenreihe des Schweizerischen Vereins für Kaltetechnik, 1, (1979)
[3]  
Lohlein, Trepp, Comparison of compression heat pump operated with one and multicomponent fluid, Int VDI Seminar ORC-HP-Technology: Working fluid problems, (1984)
[4]  
Vollmer, Kraus, Thermodynamische Stoffdaten des Kältemittelgemischs R22/R11, (1985)
[5]  
Vollmer, Ermittlung thermodynamischer Stoffdaten von Halogenkältemittelgemischen unter dem Hauptaspekt der Einsatzvorbereitung neuartiger Mehrstoffkälteanlagen in der Kälte- und Wärmepumpentechnik, Dissertation, (1987)
[6]  
Valtz, Laugier, Richon, Difluoromonochloromethane-fluorochloroethane binary mixtures, Int J Refrig, 9, pp. 283-289, (1986)
[7]  
Lavocnik, Air conditioning unit for tractor cabins, Cholodil'naja Techn, 8, pp. 33-38, (1978)
[8]  
Tan, Liu, Nan, Investigation in the cold water production system using R22/R142 for power saving, Proc XVII Int Congr Refrig, Vol B, pp. 676-687, (1987)
[9]  
Quast, Kruse, Experimental analysis for compressor behavior with non-azeotropic refrigerant mixtures, Klima Kälte Heizung, 15, pp. 493-496, (1987)
[10]  
Mulroy, Kauffeld, McLinden, Didion, An evaluation of two refrigerant mixtures in a breadboard conditioner, IIR-Meet Comm, pp. 2-10, (1988)