A FIRE DETECTION EXPERIMENT IN A WOODEN HOUSE BY SNO2 SEMICONDUCTOR GAS SENSORS

被引:13
作者
AMAMOTO, T
TANAKA, K
TAKAHATA, K
MATSUURA, S
SEIYAMA, T
机构
[1] Figaro Engineering Inc., Minoo City, Osaka, 562, 1-5-3, Senbanishi
关键词
D O I
10.1016/0925-4005(90)80206-F
中图分类号
O65 [分析化学];
学科分类号
070302 ; 081704 ;
摘要
The possibility of fire detection by SnO2 semiconductor gas sensors has been investigated in the laboratory and in a full-scale fire experiment using a wooden house. Four types of gas sensors and conventional fire detectors are compared with each other. The H2 sensor can detect the fire a few minutes earlier than conventional fire detectors. The relations between the combustion conditions and the gas sensors' responses are also discussed. © 1990.
引用
收藏
页码:226 / 230
页数:5
相关论文
共 4 条
[1]  
HANDA T, 1978, B JPN ASS FIRE SCI E, V28, P11
[2]   DETECTION OF SMOKE GASES BY SOLID-STATE SENSORS - A FOCUS ON RESEARCH ACTIVITIES [J].
PFISTER, G .
FIRE SAFETY JOURNAL, 1983, 6 (03) :165-174
[3]  
SUZUKI H, 1986, B JPN ASS FIRE SCI E, V36, P40
[4]  
1980, UPHOLSTERED FURNITUE, V725, P2556