LABORATORY TESTS TO EVALUATE HVDC WALL BUSHING PERFORMANCE IN WET WEATHER

被引:11
作者
LAMBETH, PJ [1 ]
机构
[1] INST RECH HYDRO QUEBEC, VARENNES, QUEBEC, CANADA
关键词
Booster Shed; HVDC; Non-uniform; Pollution; Rain; Wall Bushing;
D O I
10.1109/61.103674
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Two test methods have been developed to simulate the conditions causing flashover of DC wall bushings at working voltage. One is based on the clean fog pollution test. The other is a rain test, with part of the bushing unwetted. The effect of varying test parameters has been measured and five variants of the rain test have been adopted for measuring the performance of a wall bushing. Its performance compared unfavorably with that of an empty porcelain shell. Various numbers of booster sheds, (removable silicone - rubber cones fitted round the bushing) have been found to improve its performance substantially. © 1990 IEEE
引用
收藏
页码:1782 / 1793
页数:12
相关论文
共 16 条
[1]   FINAL REPORT ON THE CLEAN FOG TEST FOR HVAC INSULATORS [J].
不详 .
IEEE TRANSACTIONS ON POWER DELIVERY, 1987, 2 (04) :1317-1326
[2]   ARTIFICIAL-POLLUTION TESTS AND NATURAL-POLLUTION TESTS ON OUTDOOR 40O KV SUBSTATION INSULATORS [J].
ELY, CHA ;
KINGSTON, RG ;
LAMBETH, PJ .
PROCEEDINGS OF THE INSTITUTION OF ELECTRICAL ENGINEERS-LONDON, 1971, 118 (01) :99-&
[3]   BOOSTER SHED - PREVENTION OF FLASHOVER OF POLLUTED SUBSTATION INSULATORS IN HEAVY WETTING [J].
ELY, CHA ;
LAMBETH, PJ ;
LOOMS, JST .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1978, 97 (06) :2187-2197
[4]  
HAMMER F, 1983, 4TH INT S HIGH VOLT
[5]  
KRISHNAYYA PCCS, 1986, EL4984FR EL POW RES
[6]   VARIABLE-VOLTAGE APPLICATION FOR INSULATOR POLLUTION TESTS [J].
LAMBETH, PJ .
IEEE TRANSACTIONS ON POWER DELIVERY, 1988, 3 (04) :2103-2111
[7]  
LAMBETH PJ, 1989, CEA203T421 REP
[8]  
LAMPE W, 1984, CIGRE3301 REP
[9]  
LAMPE W, 1988, 2ND INT C PROP APPL
[10]  
MCDERMID WM, 1987, SEP P HVDC SYST OP C