INTEGRATION OF EVACUATED TUBULAR SOLAR COLLECTORS WITH LITHIUM BROMIDE ABSORPTION COOLING SYSTEMS

被引:14
作者
WARD, DS
DUFF, WS
WARD, JC
LOF, GOG
机构
[1] Solar Energy Applications Laboratory, Colorado State University, Fort Collins
关键词
D O I
10.1016/0038-092X(79)90186-5
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
By surrounding the absorber-heat exchanger component of a solar collector with a glass-enclosed evacuated space and by providing the absorber with a selective surface, solar collectors can operate at efficiencies exceeding 50 per cent under conditions of ΔT HT = 75°C m2/kW (ΔT = collector fluid inlet temperature minus ambient temperature, HT = incident solar radiation on a tilted surface). The high performance of these evacuated tubular collectors thus provides the required high temperature inputs (70-88°C) of lithium bromide absorption cooling units, while maintaining high collector efficiency. This paper deals with the performance and analysis of two types of evacuated tubular solar collectors intergrated with the two distinct solar heating and cooling systems installed on CSU Solar Houses I and III. © 1979.
引用
收藏
页码:335 / 341
页数:7
相关论文
共 4 条
[1]  
DUFF WS, 1978, JAN P ISES C NEW DEL
[2]  
Duffie J.A., 1974, SOLAR ENERGY THERMAL
[3]  
SPEYER E, 1964, J ENGNG POWER
[4]  
WARD DS, 1975, AUG P ISES C WINN