3 TERMINAL LINE PROTECTION BASED ON A SUPERIMPOSED COMPONENT IMPEDANCE RELAY

被引:8
作者
DANIEL, JS [1 ]
AGGARWAL, RK [1 ]
JOHNS, AT [1 ]
机构
[1] UNIV BATH,SCH ELECTR & ELECT ENGN,POWER & ENERGY SYST GRP,BATH BA2 7AY,AVON,ENGLAND
关键词
LINE PROTECTION; IMPEDANCE RELAY; TEED FEEDER; TRIP TIME;
D O I
10.1049/ip-c.1993.0065
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The paper presents the application of a new impedance relaying principle to a Teed feeder. The relay design is immune from false tripping owing to power swings or prefault load conditions. This has been achieved by extracting and using prefault and superimposed components of relaying voltages and currents. Results are presented for earth faults on a Teed feeder configuration. Relay trip time is typically in the range 11 to 20 ms and is plotted as a surface against pre-fault power angle and fault point on wave angle.