PD DETECTION AND LOCALIZATION BY MEANS OF ACOUSTIC MEASUREMENTS ON HYDROGENERATOR STATOR BARS

被引:14
作者
BOZZO, R [1 ]
GUASTAVINO, F [1 ]
GUERRA, G [1 ]
机构
[1] ABB CORP RES,MILAN,ITALY
关键词
D O I
10.1109/94.407030
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Acoustic partial discharge detection appears useful for the location of PD sources within various kinds of insulating systems. The usefulness of such a method to locate discharge sources in hydrogenerator stator bars is illustrated. The adopt,ed measuring procedure, based on two piezo-electric transducers positioned on a bar, allows the identification of the discharge site position within an error range of similar to 2 cm. Such a measuring procedure appears useful as a diagnostic tool in quality control for bars that do not pass the specified acceptance test or in the development of new insulating systems. The measurement circuit and the relevant test procedure are presented. Further comments about the measured acoustic velocities of the acquired signals are given.
引用
收藏
页码:660 / 666
页数:7
相关论文
共 25 条
[1]  
BARTNIKAS R, 1979, ASTM SPEICAL TECHNIC, V1, P669
[2]  
BENGTSSON T, 1992, NORD INSULATION S VA
[3]  
BOZZO R, 1994, 1994 IEEE INT S EL I, P269
[4]  
BOZZO R, 1994, 1994 C EL INS DIEL P
[5]   PD ANALYSIS OF ROTATING AC MACHINES [J].
CONTIN, A ;
RABACH, G .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1993, 28 (06) :1033-1042
[6]   PARTIAL DISCHARGES IN ELLIPSOIDAL AND SPHEROIDAL VOIDS [J].
CRICHTON, GC ;
KARLSSON, PW ;
PEDERSEN, A .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1989, 24 (02) :335-342
[7]  
FRUTH B, 1992, IEEE T ELECTR INSULA, V27
[8]   DETECTION AND LOCATION OF INTERNAL DEFECTS IN THE INSULATION OF POWER TRANSFORMERS [J].
FUHR, J ;
HAESSIG, M ;
BOSS, P ;
TSCHUDI, D ;
KING, RA .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1993, 28 (06) :1057-1067
[9]   ACOUSTICAL TECHNOLOGY APPLICATIONS IN ELECTRICAL INSULATION AND DIELECTRICS [J].
HARROLD, RT .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1985, 20 (01) :3-19
[10]  
KIMURA H, 1940, ELECTROTECH J JPN, V4, P90