THE EFFECT OF SLAT ANGLE OF WINDOWS WITH VENETIAN BLINDS ON HEATING AND COOLING LOADS OF BUILDINGS IN SOUTH-KOREA

被引:24
作者
CHO, SH
SHIN, KS
ZAHEERUDDIN, M
机构
[1] CONCORDIA UNIV,CTR BLDG STUDIES,MONTREAL,PQ H3G 1M8,CANADA
[2] KOREA INST ENERGY RES,TAEJON,SOUTH KOREA
关键词
Cooling load - Energy savings - Heating load - Slat angle - Venetian blinds;
D O I
10.1016/0360-5442(95)00074-Q
中图分类号
O414.1 [热力学];
学科分类号
摘要
The effect of slat angle and absorptance on the heating and cooling loads of buildings in Seoul (South Korea) has been studied. An analytical model of a window system with venetian blinds is developed and validated with published experimental data. The validated model has been successfully incorporated into the TRNSYS computer program. Hour-by-hour heating/cooling loads of a typical building, with and without venetian blinds, are compared. Results show that the use of windows with venetian blinds can reduce the building heating load by about 5% and cooling loads by as much as 30%.