FERRORESONANT OVERVOLTAGE CONTROL BASED ON TNA TESTS ON 3-PHASE WYE-DELTA TRANSFORMER BANKS

被引:7
作者
HOPKINSO.RH
机构
[1] General Electric Company, Electric Utility Engineering Operation, Schenectady, N.Y.
来源
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS | 1968年 / PA87卷 / 02期
关键词
D O I
10.1109/TPAS.1968.292029
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper shows possible ferroresonant overvoltages on wye-delta transformer banks during single-phase switching as a function of transformer size and lateral length. Application guide is based on industry standard voltage criteria. Secondary loading and neutral resistor requirements are given. A neutral resistor presents an attractive solution in many cases. Simple to use equations are given to allow application of test data. Copyright © 1968 by The Institute of Electrical and Electronics Engineers, Inc.
引用
收藏
页码:352 / &
相关论文
共 7 条
[1]  
Clark E., 1941, AIEE T, V60, P329
[2]  
HENDRICKSON PE, 1953, AIEE T POWER APPARAT, V72, P1183
[3]  
HOPKINSON RH, 1967, IEEE T POWER APP SYS, VPA86, P1258
[4]  
HOPKINSON RH, 1965, IEEE T POWER APP SYS, VPA84, P514
[5]  
HOPKINSON RH, 1965, IEEE T POWER APP SYS, VPA84, P289
[6]  
SCHULTZ RA, 1964 SPRING C ROCK M
[7]  
VANWORMER FC, 1965, DISTRIBUTION MAG