TRANSIENTS IN EHVDC POWER SYSTEMS .I. RECTIFIER FAULT CURRENTS

被引:9
作者
PETERSON, HA
PHADKE, AG
REITAN, DK
机构
[1] Department of Electrical Engineering, University of Wisconsin, Madison
来源
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS | 1969年 / PA88卷 / 07期
关键词
D O I
10.1109/TPAS.1969.292496
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a concise summary of results obtained from a rigorous analysis of the factors influencing the transient fault currents in an EHV rectifier terminal for a fault on the line side of the dc series reactor. The effect of the exact instant of fault occurrence after the time of completion of a commutation is shown to have special significance. It is also shown that the maximum transient peak currents, even for an “instantaneous” control system, may be on the order of 2.0 times normal or more for representative dc series inductances when initial load is considered. For a less ideal or slower control system, greater maximum peak transient fault currents are found. Furthermore, saturation of the dc series reactor is shown to result in larger currents. Results for two and three bridges in series, as well as for a single bridge, are given in curve form for convenience of the user. Copyright © 1969 by The Institute of Electrical and Electronics Engineers, Inc.