EFFECT OF ANTIOXIDANTS AND METAL DEACTIVATOR ON THE OXIDATION OF TRANSFORMER OIL

被引:12
作者
KRISHNAMOORTHY, PR
VIJAYAKUMARI, S
SANKARALINGAM, S
机构
[1] Materials Technology Division, Central Power Research Institute, Bangalore
来源
IEEE TRANSACTIONS ON ELECTRICAL INSULATION | 1992年 / 27卷 / 02期
关键词
D O I
10.1109/14.135598
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Comparative experimental data on the effectiveness of selected antioxidants and a metal deactivator in inhibiting the accelerated oxidation of reclaimed transformer oil are generated using the bomb oxidation apparatus. Energy of activation involved in the oxidation of uninhibited and inhibited oils deduced from the analysis of data are reported. Estimated lives of uninhibited and inhibited oils at the operating temperatures of transformers are also reported. Due to the difference in activation energies of inhibited oils, comparative assessment of inhibitors at a single temperature in the bomb oxidation apparatus as per standard appears to be insufficient. Among the range of antioxidants viz., monomeric and polymeric phenolic and aminic antioxidants chosen for study, the grading of only monomeric phenolic antioxidants seems to be consistent with temperature.
引用
收藏
页码:271 / 277
页数:7
相关论文
共 11 条
[1]  
DUVAL M, 1984, 8TH INT C COND BREAK, P421
[2]  
FESSLER WA, 1978, 1978 IEEE INT S EL I
[3]  
FREY RM, 1976, JUL IEEEPES SUMM M P
[4]  
KRISHNASWAMY KR, 1966, 0022INS CENTR POW RE
[5]  
LAMARRE C, 1987, CIGRE S
[6]  
WILSON ACM, 1980, INSULATING LIQUIDS T, pCH3
[7]  
ASTM D214086
[8]  
IEEE1011972 STAND
[9]  
ASTM D211286
[10]  
SEPCIFICATION NEW IN, P335