THERMODYNAMIC STUDY OF ADVANCED ABSORPTION HEAT TRANSFORMERS .1. SINGLE AND 2-STAGE CONFIGURATIONS WITH HEAT-EXCHANGERS

被引:58
作者
RIVERA, W
BEST, R
HERNANDEZ, J
HEARD, CL
HOLLAND, FA
机构
[1] Laboratorio de Energia Solar IIM-UNAM, Temixco, Morelos
[2] Departmento de Geotermia, del IIE, Cuernavaca
[3] Overseas Educational Development Office, University of Salford, Salford
来源
HEAT RECOVERY SYSTEMS & CHP | 1994年 / 14卷 / 02期
关键词
D O I
10.1016/0890-4332(94)90008-6
中图分类号
O414.1 [热力学];
学科分类号
摘要
A thermodynamic analysis was carried out to study the effect of heat exchanger effectiveness (EF) on the performance of single stage heat transformers (SSHT). Moreover, an analysis of three different arrangements of two stage heat transformers was performed using a mathematical model assuming water/lithium bromide as the working fluid. An increase in the solution heat exchanger effectiveness (EF) greatly improved the performance of absorption heat transformers when the absorber temperature was at least 40-degrees-C higher than the temperature of the heat supplied to the system. In two stage heat transformers (TSHT), higher absorber temperatures were obtained by coupling the absorber of the first stage to the evaporator of the second. However, higher performance coefficients were obtained in general by coupling the absorber of the first stage to the generator of the second.
引用
收藏
页码:173 / 183
页数:11
相关论文
共 15 条
[1]  
Altenkirch, Reversible absorptionsmachinen Zeitschrift fur die gesamte, Kalte-Industrie, 20, pp. 1-9, (1913)
[2]  
Nesselmann, Zur theorie der wärmetransformation, Wiss Veroffen-Siemens Kornzern, 12, pp. 89-109, (1933)
[3]  
Eisa, Best, Holland, Thermodynamic design data for absorption heat transformer system Part I. Operating on water/lithium bromide, J. Heat Recovery Systems, 6, pp. 421-432, (1986)
[4]  
Bokelmann, Steimle, Development of advanced absorption heat transformers utilizing new working fluids, Rev. Int. Froid, 9, pp. 51-59, (1986)
[5]  
Ciambelli, Tufano, The upgrading of waste heat by means of water/sulphuric acid absorption heat transformers, J. Heat Recovery Systems & CHP, 7, pp. 517-524, (1987)
[6]  
Mashimo, Overview of heat transformers in Japan, Proc. IEA Heat Pump Conf., pp. 271-285, (1987)
[7]  
Riesch, Scharfe, Ziegler, Volki, Alefeld, Part-Load behaviour of an absorption heat transformer, Proc. 3rd Int. Symp. on the Large Scale Applications of Heat Pump, pp. 155-160, (1987)
[8]  
Ciambelli, Tufano, On the performance of advanced absorption heat transformers Part I. The two stage configuration, J. Heat Recovery Systems & CHP, 8, pp. 445-450, (1988)
[9]  
Ciambelli, Tufano, On the performance of advanced absorption heat transformers Part II. The double absorption configuration, J. Heat Recovery Systems & CHP, 8, pp. 451-457, (1988)
[10]  
George, Srinivasa, Influence of heat exchanger effectiveness on performance of vapor absorption heat transformers, Int. J. Energy Res., 13, pp. 445-447, (1989)