HARMONIC VOLTAGES AND CURRENTS ON 2 CREEK ISLANDS WITH PHOTOVOLTAIC STATIONS - STUDY AND FIELD-MEASUREMENTS

被引:15
作者
VOKAS, GA
MACHIAS, AV
机构
[1] National Technical University, Department of Electrical Engineering, Electric Power Division, Athens, 42, 28th October St.
关键词
HARMONICS; HARMONIC CURRENTS AND VOLTAGES; INVERTERS; PHOTOVOLTAIC STATIONS; HARMONIC DISTORTION;
D O I
10.1109/60.391896
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The purpose of this paper is to investigate the harmonic distortion present to the electric grid of two small Greek islands (Arki and Antikythera) where Photovoltaic Stations are installed, to study their inverters harmonic behaviour and to present the measurements of the harmonic voltages and currents obtained at field tests on these two islands. It is shown that the harmonics injected by the Photovoltaic Stations to the electric grid are not very high and at most cases they can not cause significant problems to the appliances of the customers. On the other hand, a theoretical analysis of the installed inverters technology is also presented, showing that the results from the measurements and those of the presented analysis are quite identical. From both measurements and theoretical analysis remarkable conclusions concerning the problem of harmonics are drawn.
引用
收藏
页码:302 / 306
页数:5
相关论文
共 18 条
[1]  
Power System Harmonics - An Overview, IEEE Working Group on Power System Harmonics, PAS-102, 8, (1983)
[2]  
Arrillaga J., Bradley D.A., Bodgen P.S., Power System Harmonics, Power System Harmonics, (1985)
[3]  
Barnes R., Harmonics in Power Systems, Harmonics in Power Systems, pp. 11-15, (1989)
[4]  
The effects of Power System Harmonics on Power System Equipment and Loads, IEEE Trans.on PAS, PAS-104, (1985)
[5]  
Subjak J., McQuilkin J., Harmonics-Causes, Effects, Measurements, Analysis: An Update, Harmonics-Causes, Effects, Measurements, Analysis: An Update, 26, (1990)
[6]  
Key T.S., Evaluation of Grid-Connected Inverter Power Systems : The Utility Interface, Evaluation of Grid-Connected Inverter Power Systems : The Utility Interface, IA-20, (1984)
[7]  
Equipment Documentation, Description & Operating Instructions for Self Commutated Three-Phase Static Inverters
[8]  
Schmitt J., Unterbrechungsfreie Wechselstrom - Versorgungssysteme mit Thyristorstromrichten, Unterbrechungsfreie Wechselstrom - Versorgungssysteme mit Thyristorstromrichten, pp. 52-57, (1977)
[9]  
Clewing M., Kommutierungsvorgaenge in Selbstgefuerhten Wechselrichten, Kommutierungsvorgaenge in Selbstgefuerhten Wechselrichten, pp. 61-65, (1977)
[10]  
Vokas G., Kaminaris S., Androutsos A., Souflis J., Machias A., Papadias V., Electric Grid Problems Analysis caused by interconnected PV Stations, Electric Grid Problems Analysis caused by interconnected PV Stations, (1992)