CONTROLLING HARMONIC INSTABILITY OF HVDC LINKS CONNECTED TO WEAK AC SYSTEMS

被引:18
作者
BODGER, PS [1 ]
IRWIN, GD [1 ]
WOODFORD, DA [1 ]
机构
[1] MANITOBA HVDC RES CTR, WINNIPEG, MANITOBA, CANADA
关键词
dc transmission; harmonic instability; ratio; short circuit; weak ac system;
D O I
10.1109/61.103699
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Time domain digital simulation of HVdc transmission enables harmonic stability of a system to be studied. Two alternative measures of controlling harmonic instability were investigated; the use of C-type ac filters and a simple addition of a harmonic damping circuit in the rectifier converter control. The design of a C-type filter is described and its effectiveness presented. Harmonic damping by controls consists of taking the output from a fast response dc current transducer, passing it through a filter and a gain and adding the output to the firing angle order. Both methods result in stable recovery from faults at both rectifier and inverter terminal busbars for a dc system inherently harmonically unstable. © 1990 IEEE
引用
收藏
页码:2039 / 2046
页数:8
相关论文
共 22 条
[1]   PHASE-LOCKED OSCILLATOR - A NEW CONTROL SYSTEM FOR CONTROLLED STATIC CONVERTORS [J].
AINSWORTH, JD .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1968, PA87 (03) :859-+
[2]  
AINSWORTH JD, P I ELECTR ENG, V114, P949
[3]  
AINSWORTH JD, 1981, SEPT INT C HARM POW
[4]  
AINSWORTH JD, 1977, CIGRE14 STUD COMM
[5]   GENERALIZED METHOD OF HARMONIC REDUCTION IN AC-DC CONVERTERS BY HARMONIC CURRENT INJECTION [J].
AMETANI, A .
PROCEEDINGS OF THE INSTITUTION OF ELECTRICAL ENGINEERS-LONDON, 1972, 119 (07) :857-+
[6]  
ARRILLAGA DA, 1985, POWER SYSTEM HARMONI
[7]   INCREASING THE PULSE NUMBER OF AC-DC CONVERTERS BY CURRENT REINJECTION TECHNIQUES [J].
ARRILLAGA, J ;
JOOSTEN, APB ;
BAIRD, JF .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1983, 102 (08) :2649-2655
[8]  
Arrillaga J., 1983, HIGH VOLTAGE DIRECT
[9]   HARMONIC REDUCTION IN DC-RIPPLE REINJECTION [J].
BAIRD, JF ;
ARRILAGA, J .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1980, 127 (05) :294-303
[10]   HARMONIC REDUCTION IN MULTIPLEX CONVERTORS BY TRIPLE-FREQUENCY CURRENT INJECTION [J].
BIRD, BM ;
MARSH, JF ;
MCLELLAN, PR .