APPLIED SUPERCONDUCTIVITY ACTIVITIES AT SIEMENS

被引:2
作者
BOGNER, G
机构
[1] Siemens Research Laboratories
关键词
D O I
10.1109/TMAG.1979.1060113
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A 35 m long semiflexible single phase ac test cable for 110 kV and 10 kA with full load terminations was successfully tested with respect to its cryogenic and electrical behaviour. Within the development of two-pole generators with output ratings from 1000 to 3000 MVA the electrical losses of appropriate field winding conductors are determined under transient operation conditions. The characteristics of a rotating bath cooling are investigated with special emphasis on stability problems. Experimental studies on structural rotor materials are also being carried out. In the course of our work on magnetic levitation a 17 tons test carrier has been levitated several times at an air gap of 100 mm and speeds up to 150 km/h. At present a linear synchronous motor with superconducting field windings and active track is just before completion and will go into operation late 1978. With regard to the future European fusion program and the US-DOE Large Coil Task (LCT) we have initiated activities on the development and fabrication of large D-shaped magnets. © 1979 IEEE
引用
收藏
页码:824 / 827
页数:4
相关论文
共 6 条
[1]  
ALBRECHT C, 1977, 6TH P INT C MAGN TEC, P177
[2]   35-M SUPERCONDUCTING CABLE TEST FACILITY [J].
BOGNER, G ;
PENCZYNSKI, P ;
SCHMIDT, F .
IEEE TRANSACTIONS ON MAGNETICS, 1977, 13 (01) :400-403
[3]  
HAUBENREICH PN, 1977, 7TH P S ENG PROBL FU, V2, P916
[4]  
KULLMANN D, 1977, 6TH P INT C MAGN TEC, P189
[5]  
SCHNAPPER C, 1978, PROG FROID TRES BASS, P217
[6]  
1977, BMFTET4042A CONTR