GENERATOR INSULATION DIAGNOSTIC TESTING

被引:28
作者
KURTZ, M
LYLES, JF
机构
[1] Ontario Hydro, Toronto
来源
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS | 1979年 / 98卷 / 05期
关键词
D O I
10.1109/TPAS.1979.319475
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Ontario Hydro's experience with diagnostic partial discharge tests on hydraulic generators over a period of five years shows that a reliable prediction of stator insulation condition can be made prior to physical examination. “Action limit values” have been established to this end. This paper gives a brief historical review of problems encountered, and a description of repair procedures on windings with slot discharge/mechanical abrasion insulation damage. Recent advances in the diagnostic test equipment and technique for reducing test cost and increasing test credibility are briefly described. Copyright © 1979 by The Institute of Electrical and Electronics Engineers. Inc.