TRACER-GAS TECHNIQUES FOR MEASURING VENTILATION IN A SINGLE ZONE

被引:224
作者
SHERMAN, MH
机构
[1] Energy Performance of Buildings Group, Applied Science Division, Lawrence Berkeley Laboratory, Berkeley
关键词
Gas Injection Strategies - Tracer Gases;
D O I
10.1016/0360-1323(90)90010-O
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Tracer-gas techniques have become widely used to measure the ventilation rates in buildings. A tracer gas is an idealized substance used to tag volumes of air so as to be able to infer their bulk movement; the properties of a perfect tracer are discussed. The basic principle involved is that of conservation of mass (of both air and tracer gas) as expressed in the continuity equation; by monitoring the injection and concentration of the tracer, one can infer the exchange of air. This report will summarize the techniques in use. Although there is only one continuity equation, there are many different experimental injection strategies and analytical approaches. These different techniques may result in different estimates of ventilation due to uncertainties and biases of the procedures. This report will analyse the spectrum of techniques, including some of the relevant error analyses. © 1990.
引用
收藏
页码:365 / 374
页数:10
相关论文
共 32 条
[11]  
Collins, Smith, Measurements of ventilation rates using a radioactive tracer, J. Inst. Heat Vent. Engrs, 23, pp. 270-274, (1955)
[12]  
Howland, Kimber, Littlejohn, Measurements of air movements in a house using a radioactive tracer gas, J. Inst. Heat Vent. Engrs., 28, pp. 57-71, (1960)
[13]  
Lidwell, The evaluation of ventilation, J. Hyg., 58, pp. 297-305, (1960)
[14]  
Howard, Ventilation measurements in houses and the influence of wall ventilators, Bldg Sci., 1, pp. 251-257, (1966)
[15]  
Hunt, Burch, Air infiltration measurements in a four-bedroom townhouse using sulfur hexafluoride as a tracer gas, ASHRAE Trans. I., 81, pp. 186-201, (1975)
[16]  
Grimsrud, Sherman, Janssen, Pearman, Harrje, An intercomparison of tracer gases used for air infiltration, ASHRAE Trans., 86, pp. 258-267, (1980)
[17]  
Grimsrud, Sherman, Janssen, Pearman, Harrje, Lawrence Berkeley Laboratory Report, LBL-8394, (1979)
[18]  
Harrje, Et al., Tracer gas measurement systems compared in multifamily and commercial buildings, ASTM STP 1067, Air Change Rate and Air Tightness in Buildings, (1990)
[19]  
Sandberg, Sjoberg, The use of moments for assessing air quality in ventilated rooms, Bldg Envir., 18, (1983)
[20]  
Axley, Multi-zone contaminant dispersal analysis using an element assembly approach, Proceedings of the 9th AIVC Conference on Effective Ventilation, 2, (1988)