IMPROVEMENTS TO A STANDARD AUTOMATIC-GENERATION CONTROL FILTER ALGORITHM

被引:10
作者
PROWSE, DCH
机构
[1] Manitoba Hydro, Winnipeg, Manitoba
关键词
AUTOMATIC GENERATION CONTROL; AREA CONTROL ERROR; FILTER; MODELING; NONLINEAR OPTIMIZATION; JOINT AGC;
D O I
10.1109/59.260876
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 [电气工程]; 0809 [电子科学与技术];
摘要
Tuning a standard digital implementation of a filter for Automatic Generation Control involves a compromise between achieving inensitivity to small random load fluctuations and ensuring a prompt, stable response to a power system disturbance. A personal computer-based AGC simulation program and non-linear optimization logic were used to develop an Area Control Error filter algorithm that reduces the amount of control action and improves control performance. Implementation on the Manitoba Hydro 4500 MW system indicated a substantial (about 80%) reduction in control pulses compared to the standard AGC filter design provided with the AGC/SCADA system. Significant improvement has been observed both during periods of regulation for Manitoba Hydro alone and during periods of Joint AGC operation in which Manitoba Hydro also provides AGC regulation services for three neighbouring utilities.
引用
收藏
页码:1204 / 1210
页数:7
相关论文
共 13 条
[1]
BOX MJ, 1969, NONLINEAR OPTIMIZATI
[2]
Cohn N, 1966, CONTROL GENERATION P
[3]
COHN N, 1950, POWER FLOW CONTROL B
[4]
AUTOMATIC GENERATION CONTROL .2. DIGITAL CONTROL TECHNIQUES [J].
DEMELLO, FP ;
MILLS, RJ ;
BRELLS, WF .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1973, PA92 (02) :716-724
[5]
AUTOMATIC GENERATION CONTROL .2. DIGITAL CONTROL TECHNIQUES [J].
DEMELLO, FP ;
MILLS, RJ ;
BRELLS, WF .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1973, PA92 (02) :716-724
[6]
FLEMING RJ, 1984, MAY US PERF IND ADJ, P15
[7]
COST ASPECTS OF AGC, INADVERTENT ENERGY AND TIME ERROR [J].
HENDERSON, PD ;
KLAIMAN, H ;
GINNETTI, J ;
SNODGRASS, T ;
COHN, N ;
BLOOR, S ;
VANSLYCK, L .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1990, 5 (01) :111-118
[8]
KUMAR K, 1989, FILTER IMPROVED PERF, P5
[9]
A LOAD FREQUENCY CONTROL ALGORITHM BASED ON A GENERALIZED-APPROACH [J].
MALIK, OP ;
KUMAR, A ;
HOPE, GS .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1988, 3 (02) :375-382
[10]
TAYLOR CW, 1976, IEEE T PS