THE RELATION BETWEEN THERMAL AND ELECTRICAL STRESS AND THE PD BEHAVIOR OF EPOXY-RESIN TRANSFORMERS

被引:12
作者
BORSI, H
机构
[1] Schering Institute, High Voltage Technique and Engineering, University of Hannover, Hannover
来源
IEEE TRANSACTIONS ON ELECTRICAL INSULATION | 1993年 / 28卷 / 06期
关键词
D O I
10.1109/14.249374
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper deals with the PD behavior of epoxy resin transformer coils in a temperature range between -30 and 180 degrees C. In particular the PD inception voltage as a very important parameter for the judgement of the PD characteristic of a transformer over the temperature is considered. The PD inception voltage is determined at different static temperatures in step test. The tempering of the coils occur from the outside by submerging the coil in tempered fluid, as well as from inside, with the help of current losses. Models of HV coils of distribution transformers are used as specimen. The windings of the coils consist of wires which have different insulation. Some windings consist of wires with a thin layer of varnish. The others have wires with a glass-silk wrapped insulation. The dependencies between the PD inception voltage of the coils and parameters such as wire insulation and inner or outer tempering are determined and discussed. Furthermore the results of long term tests are introduced in which five coils are stressed with a voltage of 1.75 kV at a temperature of 175 degrees C for a duration of 1 yr. During this time PD measurements with a sensitivity of 2 pC were carried out.
引用
收藏
页码:1007 / 1015
页数:9
相关论文
共 18 条
[11]  
Cachay O.E., Das Teiientladungs (TE)-Verhalten von GieBharzimprägnierten Transformatorapulen, (1990)
[12]  
Borsi H.O., Cachay E., Partial Discharge Behavior of Epoxy Resin, Impregnated Transformer Coils, IEEE Trans. on Electrical Insulation, 27, pp. 1118-1126, (1992)
[13]  
Bammert U., Beyer M., Schroder U., Automa-tisiertes Meßsystem Zur Erfassung und Verarbeitung von Teilentladungen in Isolierstoffen bei Langzeitun-tersuchungen, Technisches Messen, 3, pp. 97-103, (1986)
[14]  
Beyer M., Borsi H., Oelert L., Investigation of Damage-behavior in Cast Epoxy Resin Coils under Thermal and Electrical Stress with the Help of Partial Discharge (PD) Measurements, (1991)
[15]  
Bachofen F., Beyer M., Jahne H-J., Einfluß Mecha-nischer Spannungen Und Elektrischer Beanspruchung Auf Das Teilentladungsver-halten von Epoxidharz, (1975)
[16]  
Beyer M., Jahne H.-J., vonOlshausen R., Beeinflus-sung der Anlaufphase Des Teilentladungsverhaltens von Epoxidharz Durch Feldstärke, Temperatur und Innere Mechanische Spannungen, ETZ-A, 99, pp. 324-327, (1978)
[17]  
Beyer M., Borsi H., Cachay O., Influence of Temperatnre and Stress on the Partial Discharge (PD) Behavior of Epoxy Resin-cast Transformer Coils, (1991)
[18]  
Beyer M., Borsi H., Oelert L., Einfluß Kombinierter Thermischer und Elektrischer Beanspruchung Auf Das Teilentladungs (TE)-verhalten Gießharzimpräg-nierterspulen ETG-Fachtagung Isoriersysteme der Elektrischen Energietechnik, (1992)