Combined Active Islanding Detection Method for Grid-connected Photovoltaic System

被引:3
作者
WEI Quan [1 ,2 ]
WANG Yifei [1 ]
ZHU Jing [1 ]
YIN Xiaogang [1 ]
LIU Zhuang [1 ]
机构
[1] Xi'an High Voltage Apparatus Research Institute Co, Ltd
[2] Xi'an Jiaotong University
关键词
D O I
10.13296/j.1001-1609.hva.2014.10.031
中图分类号
TM464 [逆变器];
学科分类号
080508 [光电信息材料与器件];
摘要
Unintentional islanding phenomenon has been one of the most important problems of gridconnected photovoltaic inverters. To prevent this phenomenon, all kinds of anti-islanding methods have been discussed. This paper presents a combined active islanding detection method, which consists of active frequency drift method and automatic phase-shift method. The traditional active anti-islanding methods of grid-connected PV inverters bear nondetection zone possibilities for certain paralleled RLC loads. The combined method shows islanding detection ability effectively, and it can eliminate nondetection zones even in the worst case conditions. Simulation in different load conditions is performed for verification.
引用
收藏
页码:37 / 42
页数:6
相关论文
共 3 条
[1]
A combined active anti-islanding method for photovoltaic systems.[J].Byunggyu Yu;Mikihiko Matsui;Youngseok Jung;Gwonjong Yu.Renewable Energy.2007, 5
[2]
Modeling and design of phase shift anti-islanding method using non-detection zone [J].
Yu, Byunggyu ;
Matsui, Mikihiko ;
Jung, Youngseok ;
Yu, Gwonjong .
SOLAR ENERGY, 2007, 81 (11) :1333-1339
[3]
Prevention of islanding in grid-connected photovoltaic systems [J].
Ropp, ME ;
Begovic, M ;
Rohatgi, P .
PROGRESS IN PHOTOVOLTAICS, 1999, 7 (01) :39-59