应用增爬群改善大雨条件下800 kV叠锥型支柱绝缘子的雨闪性能(英文)

被引:5
作者
Orsino Oliveira Filho [1 ]
Jos Antonio Cardoso [1 ]
Darcy Ramalho de Mello [1 ]
Rogrio Magalhes de Azevedo [1 ]
Sylvia G Carvalho [2 ]
机构
[1] Cepel-Electric Energy Research Center,Zip Code - Rio de Janeiro,RJ,Brazil
[2] Eletrobras Furnas-Centrais Eletricas S/A Zip Code - Rio de Janeiro,RJ,Brazil
关键词
UHV insulator; heavy rain; booster sheds; wet tests; disruptive discharge; ultra-violet images;
D O I
10.13336/j.1003-6520.hve.2011.11.024
中图分类号
TM216 [绝缘子和套管];
学科分类号
0805 ; 080502 ; 080801 ;
摘要
<正>Studies based on AC high voltage tests have been done at Cepel to investigate the performance of 800 kV busbar insulators under heavy wetting conditions.Insulators were tested which are now used on site and also with different configurations of booster sheds.Images recorded by ultra-violet(UV) camera were used to help the investigations on the effectiveness of booster sheds.By comparing UV images of the insulator being stressed with high voltage under heavy artificial rain,with and without booster sheds,it was possible to observe how significant the reduction on the flashover formation process was when booster sheds were used.The effectiveness of booster sheds was also quantified by determining the disruptive discharge of the insulator with and without them.The results of these studies can also be considered as contribution to national and international standard technical committees to improving the standardized procedure for tests on ultra high voltage(UHV) insulators under heavy rain.Subjects such as the clear definition of relevant UHV test procedure and test arrangements,including the use of UV camera,have to be taken into account.
引用
收藏
页码:2772 / 2779
页数:8
相关论文
共 1 条
[1]   800kV叠装式瓷绝缘子大雨下的性能评估(英文) [J].
Orsino Oliveira Filho ;
Darcy RMello ;
Jos ACardoso ;
Rogrio Mde Azevedo ;
Sylvia GCarvalho ;
Waldenir ASCruz .
高电压技术, 2008, 34 (12) :2552-2557