Wind Farms Fault Ride Through Using DFIG With New Protection Scheme

被引:183
作者
Okedu, Kenneth E. [1 ]
Muyeen, S. M. [2 ]
Takahashi, Rion [1 ]
Tamura, Junji [1 ]
机构
[1] Kitami Inst Technol, Dept Elect & Elect Engn, Sapporo, Hokkaido 0908507, Japan
[2] Petr Inst, Dept Elect Engn, Abu Dhabi, U Arab Emirates
关键词
Doubly fed induction generator (DFIG); induction generator (IG); protection schemes; series dynamic braking resistor (SDBR); stability; wind energy; wind farms; FED INDUCTION GENERATOR; DYNAMIC-BEHAVIOR; TRANSIENT STABILITY; SYSTEM; TURBINES; MACHINES; CROWBAR;
D O I
10.1109/TSTE.2011.2175756
中图分类号
X [环境科学、安全科学];
学科分类号
083001 [环境科学];
摘要
This paper proposes a control strategy of doubly fed induction generators (DFIGs) with new protection schemes for enhancing fault ride through capability of wind farms composed of DFIGs and induction generators (IGs). Since the DFIGs will be stressed or overloaded in the process of stabilizing the wind farm during a grid fault, it is paramount to consider a protection scheme for the DFIG, in order to protect its power converters. Two schemes, the dc-link chopper-controlled braking resistor with the supplementary rotor current (SRC) control of the rotor side converter of the DFIG and series dynamic braking resistor (SDBR) connected to the stator of the DFIG, are proposed and compared. Merits and drawbacks of both schemes are highlighted as well. The simulation results in power system computer aided design and electromagnetic transient including DC (PSCAD/EMTDC) show that the two proposed schemes can eliminate the need for an expensive crowbar switch in the rotor circuit, because both could limit the rotor current of the DFIG within its nominal value during a grid fault. Finally, considering the overall system performance, the latter is recommended.
引用
收藏
页码:242 / 254
页数:13
相关论文
共 38 条
[1]
Mitigation of unbalanced voltage dips using static series compensator [J].
Awad, H ;
Svensson, J ;
Bollen, M .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2004, 19 (03) :837-846
[2]
Fault ride-through of large wind farms using series dynamic braking resistors (March 2007) [J].
Causebrook, Andrew ;
Atkinson, David J. ;
Jack, Alan G. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2007, 22 (03) :966-975
[3]
Improving power system dynamic behavior through doubly fed induction machines controlled by static converter using fuzzy control [J].
de Almeida, RG ;
Lopes, JAP ;
Barreiros, JAL .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2004, 19 (04) :1942-1950
[4]
HYDRAULIC-TURBINE AND TURBINE CONTROL-MODELS FOR SYSTEM DYNAMIC STUDIES [J].
DEMELLO, FP ;
KOESSLER, RJ ;
AGEE, J ;
ANDERSON, PM ;
DOUDNA, JH ;
FISH, JH ;
HAMM, PAL ;
KUNDUR, P ;
LEE, DC ;
ROGERS, GJ ;
TAYLOR, C .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1992, 7 (01) :167-179
[5]
[6]
Modeling of wind turbines based on doubly-fed induction generators for power system stability studies [J].
Erlich, Istvan ;
Kretschmann, Joerg ;
Fortmann, Jens ;
Mueller-Engelhardt, Stephan ;
Wrede, Holger .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2007, 22 (03) :909-919
[7]
A fault tolerant doubly fed induction generator wind turbine using a parallel grid side rectifier and series grid side converter [J].
Flannery, Patrick S. ;
Venkataramanan, Giri .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2008, 23 (03) :1126-1135
[8]
Ibrahim AO, 2009, P IEEE EN CONV C EXP
[9]
IEEE Std, 1992, 4215 IEEE
[10]
Wind turbines based on doubly fed induction generator under asymmetrical voltage dips [J].
Lopez, Jesus ;
Gubia, Eugenio ;
Sanchis, Pablo ;
Roboam, Xavier ;
Marroyo, Luis .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2008, 23 (01) :321-330