CFD study on micro-environment around human body and personalized ventilation

被引:167
作者
Gao, NP [1 ]
Niu, JL [1 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Hong Kong, Hong Kong, Peoples R China
关键词
personalized ventilation; thermal plume; pollutant exposure reduction; personalized air utilization efficiency;
D O I
10.1016/j.buildenv.2004.01.026
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
A seated computational thermal manikin (CTM) with geometry of a real human body is used to study the micro-environment around human body with and without personalized ventilation (PV) system. Two novel evaluation indices, pollutant exposure reduction and personalized air utilization efficiency, are introduced. In the range of the personalized airflow rate from 0.0 to 3.0 l/s, the best inhaled air quality is achieved at the airflow rate of 0.8 l/s in the numerical simulation, whereas in our earlier experiments this occurred at the maximum flow rate 3.0 l/s. Through detailed analysis of interaction between thermal plume around human body and personalized airflow, the mechanism of inhalation process becomes more perspicuous. Results from computational fluid dynamics (CFD) and experiment are compared and improvements of CFD simulation accuracy are recommended. (C) 2004 Elsevier Ltd. All rights reserved.
引用
收藏
页码:795 / 805
页数:11
相关论文
共 28 条
[1]  
[Anonymous], P ROOMVENT 92 AIR DI
[2]  
ASHRAE, 1992, 551992 ASHRAE ANSI
[3]  
BERGLUND L, 1989, P IAQ 89 HUM EQ HLTH, P93
[4]  
Brohus H., 1996, P 5 INT C AIR DISTR, P137
[5]  
Brohus H, 1997, PERSONAL EXPOSURE CO, P61
[6]  
CHANG SKW, 1991, ASHRAE TRAN, V97, P31
[7]  
CHANG SKW, 1993, ASHRAE TRAN, V99, P450
[8]   Convective and radiative heat transfer coefficients for individual human body segments [J].
deDear, RJ ;
Arens, E ;
Hui, Z ;
Oguro, M .
INTERNATIONAL JOURNAL OF BIOMETEOROLOGY, 1997, 40 (03) :141-156
[9]   Impact of temperature and humidity on the perception of indoor air quality [J].
Fang, L ;
Clausen, G ;
Fanger, PO .
INDOOR AIR-INTERNATIONAL JOURNAL OF INDOOR AIR QUALITY AND CLIMATE, 1998, 8 (02) :80-90
[10]   Indoor air quality in the 21st century: Search for excellence [J].
Fanger, PO .
INDOOR AIR, 2000, 10 (02) :68-73