Low-voltage ride-through of a full converter wind turbine with permanent magnet generator

被引:230
作者
Conroy, J. F. [1 ]
Watson, R. [1 ]
机构
[1] Univ Coll Dublin, Dept Elect Elect & Mech Engn, UCD Belfield, Dublin 4, Ireland
关键词
D O I
10.1049/iet-rpg:20070033
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
The low-voltage ride-through capability of a 2 MW full converter wind turbine with permanent magnet synchronous generator is investigated herein. A detailed description of the system, its controller options and its behaviour when subjected to a severe voltage dip, is presented. A control scheme for the turbine that allows it to withstand severe voltage dips is designed and simulated. This control scheme emphasises the regulation of the dc-link voltage and minimisation of the drive train torque surplus. Also, the level of modelling detail required for stability analysis is analysed and discussed.