Quantitative Analysis of Ageing Condition of Oil-paper Insulation by Frequency Domain Spectroscopy

被引:79
作者
Liao, Ruijin [1 ]
Hao, Jian [1 ,2 ]
Chen, G. [2 ]
Yang, Lijun [1 ]
机构
[1] Chongqing Univ, State Key Lab Power Transmiss Equipment & Syst Se, Chongqing 400044, Peoples R China
[2] Univ Southampton, Sch Elect & Comp Sci, Southampton SO17 1BJ, Hants, England
关键词
Frequency domain spectroscopy; oil-paper insulation; ageing condition; permittivity; dielectric loss; quantitative analysis; DIELECTRIC RESPONSE; IMPREGNATED CELLULOSE; MOISTURE; TEMPERATURE; DEGRADATION;
D O I
10.1109/TDEI.2012.6215085
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Frequency domain spectroscopy (FDS) has been used to assess the ageing condition of oil-paper insulation used in transformers. To further understand the ageing process, the reduction in degree of polymerization (DP) of cellulosic paper in itself on the dielectric response was investigated first. It has been found that the reduction in DP itself can alter the dielectric characteristics. The oil-paper insulation was thermally accelerated aged at 110 degrees C for up to 154 days according to the procedure described in IEEE Guide. Then dielectric characteristics of the thermally aged samples were obtained at different measurement temperatures. The results reveal that the relative permittivity (epsilon(r)') plots of oil impregnated pressboards increase with the reduction in cellulose polymer chain length. epsilon(r)' and tan delta values of oil impregnated pressboards shifts upwards in the lower frequency range (10(-3) Hz-10(-1) Hz) with different ageing condition, indicating the possibility of utilizing the characteristics of. epsilon(r)' and tan delta values at lower frequencies (10-3 Hz-10-1 Hz) to quantitatively characterize ageing condition of oil impregnated pressboard. The parameters including DP, epsilon(r)' and tan delta values at the three characteristic frequencies (10(-3) Hz, 10(-2) Hz, 10(-1) Hz) have been analyzed as a function of the ageing time, showing an exponential relationship based on the best fit. In addition, the epsilon(r)' and tan delta curves of aged oil impregnated pressboard have been observed to be shifted upwards to higher values at lower frequencies when the measurement temperature is increased. A shifting factor alpha(T) which describes the relationship between frequency and temperature has been defined. It allows one to shift the master curve of impregnated pressboard with DP obtained at reference temperature to other testing temperatures.
引用
收藏
页码:821 / 830
页数:10
相关论文
共 30 条
[1]  
[Anonymous], 2002, 150109 CIGRE TASK FO
[2]  
[Anonymous], 2008, IEEE INT C DIELECTR
[3]  
[Anonymous], C57911995 IEEE
[4]  
[Anonymous], 20 INT POW SYST C AM
[5]   Frequency response of oil impregnated pressboard and paper samples for estimating moisture in transformer insulation [J].
Ekanayake, Chandima ;
Gubanski, Stanislaw M. ;
Graczkowski, Andrzej ;
Walczak, Krzysztof .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (03) :1309-1317
[6]  
El-Henawii SA, 1999, J MATER SCI TECHNOL, V15, P164
[7]   REVIEW OF CHEMICAL INDICATORS OF DEGRADATION OF CELLULOSIC ELECTRICAL PAPER INSULATION IN OIL-FILLED TRANSFORMERS [J].
EMSLEY, AM ;
STEVENS, GC .
IEE PROCEEDINGS-SCIENCE MEASUREMENT AND TECHNOLOGY, 1994, 141 (05) :324-334
[8]  
Gäfvert U, 2000, PROCEEDINGS OF THE 6TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1 & 2, P825, DOI 10.1109/ICPADM.2000.876357
[9]   Dielectric response methods for diagnostics of power transformers [J].
Gubanski, SM ;
Boss, P ;
Csépes, G ;
Houhanessian, VD ;
Filippini, J ;
Guuinic, P ;
Gäfvert, U ;
Karius, V ;
Lapworth, J ;
Urbani, G ;
Werelius, P ;
Zaengl, W .
IEEE ELECTRICAL INSULATION MAGAZINE, 2003, 19 (03) :12-18
[10]   Dielectric response measurements in time and frequency domain on high voltage insulation with different response [J].
Helgeson, A ;
Gäfvert, U .
1998 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING MATERIALS, PROCEEDINGS, 1998, :393-398