Effect of strip location on the air-side pressure drop and heat transfer in strip fin-and-tube heat exchanger

被引:66
作者
Kang, HC [1 ]
Kim, MH
机构
[1] Kunsan Natl Univ, Sch Mech Engn, Kunsan 573701, South Korea
[2] Pohang Univ Sci & Technol, Dept Mech Engn, Pohang 790784, South Korea
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 1999年 / 22卷 / 04期
关键词
heat exchanger; finned heat exchanger; fin; heat transfer coefficient;
D O I
10.1016/S0140-7007(98)00062-0
中图分类号
O414.1 [热力学];
学科分类号
摘要
This work discusses about the pressure drop and heat transfer characteristics of a plain fin, a strip fin and combinations thereof in the fin-and-tube heat exchanger. Experimental apparatus and test algorithm using scale-up model fin geometry are discussed. The present work uses the electric heaters inside of the tube as the heating source to simulate the hot water loop in the wind tunnel test. The test results of the plain and strip fins are compared with the existing correlation and experimental data. It was found that a hybrid fin, plain fin at front row and strip fin at rear row, was more effective to enhance the heat transfer than that of the whole strip fin at the same fan power. (C) 1999 Elsevier Science Ltd and IIR. All rights reserved.
引用
收藏
页码:302 / 312
页数:11
相关论文
共 17 条
[11]  
NAKAYAMA W, 1983, ASME JSME THERM ENG, V1, P495
[12]  
RAE WH, 1984, LOW SPEED WIND TUNNE
[13]  
Shah R. K., 1978, Sixth International Heat Transfer Conference, P193
[14]  
TANAKA T, 1984, B JSME, V27, P219
[15]   Heat transfer and friction characteristics of typical wavy fin-and-tube heat exchangers [J].
Wang, CC ;
Fu, WL ;
Chang, CT .
EXPERIMENTAL THERMAL AND FLUID SCIENCE, 1997, 14 (02) :174-186
[16]   Heat transfer and friction characteristics of convex-louver fin-and-tube heat exchangers [J].
Wang, CC ;
Chen, PY ;
Jang, JY .
EXPERIMENTAL HEAT TRANSFER, 1996, 9 (01) :61-78
[17]  
WEBB RL, 1990, ASHRAE TRAN, V96, P445