Active Harmonic Filtering Using Current-Controlled, Grid-Connected DG Units With Closed-Loop Power Control

被引:190
作者
He, Jinwei [1 ]
Li, Yun Wei [1 ]
Blaabjerg, Frede [2 ]
Wang, Xiongfei [2 ]
机构
[1] Univ Alberta, Dept Elect & Comp Engn, Edmonton, AB T6G 2R3, Canada
[2] Aalborg Univ, Dept Elect & Comp Engn, DK-9220 Aalborg, Denmark
关键词
Active power filter; distributed generation; harmonic compensation; harmonic extraction; phase-locked loop (PLL); resonant controller; virtual impedance; CONTROL STRATEGY; REACTIVE POWER; COMPENSATION; SYNCHRONIZATION; CONVERTERS; INTERFACE; INVERTERS; DESIGN; SYSTEM;
D O I
10.1109/TPEL.2013.2255895
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The increasing application of nonlinear loads may cause distribution system power quality issues. In order to utilize distributed generation (DG) unit interfacing converters to actively compensate harmonics, this paper proposes an enhanced current control approach, which seamlessly integrates system harmonic mitigation capabilities with the primary DG power generation function. As the proposed current controller has two well-decoupled control branches to independently control fundamental and harmonic DG currents, local nonlinear load harmonic current detection and distribution system harmonic voltage detection are not necessary for the proposed harmonic compensation method. Moreover, a closed-loop power control scheme is employed to directly derive the fundamental current reference without using any phase-locked loops (PLL). The proposed power control scheme effectively eliminates the impacts of steady-state fundamental current tracking errors in the DG units. Thus, an accurate power control is realized even when the harmonic compensation functions are activated. In addition, this paper also briefly discusses the performance of the proposed method when DG unit is connected to a grid with frequency deviation. Simulated and experimental results from a single-phase DG unit validate the correctness of the proposed methods.
引用
收藏
页码:642 / 653
页数:12
相关论文
共 35 条
[1]   Control strategy and site selection of a shunt active filter for damping of harmonic propagation in power distribution systems [J].
Akagi, H .
IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (01) :354-363
[2]   INSTANTANEOUS REACTIVE POWER COMPENSATORS COMPRISING SWITCHING DEVICES WITHOUT ENERGY-STORAGE COMPONENTS [J].
AKAGI, H ;
KANAZAWA, Y ;
NABAE, A .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1984, 20 (03) :625-630
[3]   A shunt active filter based on voltage detection for harmonic termination of a radial power distribution line [J].
Akagi, H ;
Fujita, H ;
Wada, K .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1999, 35 (03) :638-645
[4]  
[Anonymous], INSTANTANEOUS POWER
[5]  
[Anonymous], 2000, 9292000 IEEE
[6]   Detection is key - Harmonic detection methods for active power filter applications [J].
Asiminciaei, Lucian ;
Blaabjerg, Frede ;
Hansen, Steffan .
IEEE INDUSTRY APPLICATIONS MAGAZINE, 2007, 13 (04) :22-33
[7]   Adaptive compensation of reactive power with shunt active power filters [J].
Asiminoaei, Lucian ;
Blaabjerg, Frede ;
Hansen, Steffan ;
Thogersen, Paul .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2008, 44 (03) :867-877
[8]   Power electronics as efficient interface in dispersed power generation systems [J].
Blaabjerg, F ;
Chen, Z ;
Kjaer, SB .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2004, 19 (05) :1184-1194
[9]   Enhanced Power Quality Control Strategy for Single-Phase Inverters in Distributed Generation Systems [J].
Bojoi, Radu Iustin ;
Limongi, Leonardo Rodrigues ;
Roiu, Daniel ;
Tenconi, Alberto .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2011, 26 (03) :798-806
[10]   Current control strategy for power conditioners using sinusoidal signal integrators in synchronous reference frame [J].
Bojoi, RI ;
Griva, G ;
Bostan, V ;
Guerriero, M ;
Farina, F ;
Profumo, F .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2005, 20 (06) :1402-1412