Control strategy and site selection of a shunt active filter for damping of harmonic propagation in power distribution systems

被引:245
作者
Akagi, H
机构
[1] Department of Electrical Engineering, Okayama University, Okayama-city
关键词
D O I
10.1109/61.568259
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper deals with a shunt active filter which will be installed by an electric utility, putting much emphasis on the control strategy and the best point of installation of the shunt active filter on a feeder in a power distribution system. The objective of the shunt active filter is to damp harmonic propagation, which results from harmonic resonance between many capacitors for power factor improvement and line inductors in the feeder, rather than to minimize voltage distortion throughout the feeder. Harmonic mitigation is a welcome ''by-product'' of the shunt active filter, which comes from damping of harmonic propagation. This paper concludes that the shunt active filter based on detection of voltage at the point of installation is superior in stability to others, and that the best site selection is not the beginning terminal but the end terminal of the primary line in the feeder. Computer simulation is performed to verify the validity and effectiveness of the shunt active filter by means of an analog circuit simulator, which is characterized by installing it on a feeder of a radial distribution system in a residential area.
引用
收藏
页码:354 / 363
页数:10
相关论文
共 16 条
[1]   TRENDS IN ACTIVE POWER-LINE CONDITIONERS [J].
AKAGI, H .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 1994, 9 (03) :263-268
[2]   CONTROL STRATEGY OF ACTIVE POWER FILTERS USING MULTIPLE VOLTAGE-SOURCE PWM CONVERTERS [J].
AKAGI, H ;
NABAE, A ;
ATOH, S .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1986, 22 (03) :460-465
[3]  
[Anonymous], 1971, DIRECT CURRENT TRANS
[4]  
[Anonymous], P 1983 INT POW EL C
[5]  
Arrillaga J., 1985, Power System Harmonics
[6]   THE APPLICATION OF NETWORK OBJECTIVE FUNCTIONS FOR ACTIVELY MINIMIZING THE IMPACT OF VOLTAGE HARMONICS IN POWER-SYSTEMS [J].
GRADY, WM ;
SAMOTYJ, MJ ;
NOYOLA, AH ;
ELAMIN, IM ;
MASOUM, MAS ;
FUCHS, EF .
IEEE TRANSACTIONS ON POWER DELIVERY, 1992, 7 (03) :1379-1386
[7]   SURVEY OF ACTIVE POWER-LINE CONDITIONING METHODOLOGIES [J].
GRADY, WM ;
SAMOTYJ, MJ ;
NOYOLA, AH .
IEEE TRANSACTIONS ON POWER DELIVERY, 1990, 5 (03) :1536-1542
[8]  
Gyugyi L., 1976, Active ac power filters, P529
[9]  
IIZUKA A, 1995, P 1995 INT POW EL C, P609
[10]   A NEW APPROACH TO HARMONIC COMPENSATION IN POWER-SYSTEMS - A COMBINED SYSTEM OF SHUNT PASSIVE AND SERIES ACTIVE-FILTERS [J].
PENG, FZ ;
AKAGI, H ;
NABAE, A .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1990, 26 (06) :983-990