Implementation and performance of automatic gain adjustment in a shunt active filter for harmonic damping throughout a power distribution system

被引:94
作者
Jintakosonwit, P [1 ]
Akagi, H
Fujita, H
Ogasawara, S
机构
[1] Tokyo Inst Technol, Tokyo 1528552, Japan
[2] Okayama Univ, Okayama 7008530, Japan
关键词
D O I
10.1109/TPEL.2002.1004252
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper discusses automatic gain adjustment in a fully-digital-controlled shunt active filter. This is the first step in cooperative control of the multiple active filters based on voltage detection for harmonic damping throughout power distribution systems. In general, the active filter should be equipped with an optimal control gain corresponding to the characteristic impedance of a distribution line. However, it is difficult to know circuit parameters of a real distribution line having various shunt capacitors and loads. Therefore, a main purpose of the gain adjustment is to make the active filter damp out harmonic propagation without considering the circuit parameters. In addition, the gain adjustment can reduce the compensating currents and losses in the active filter, and moreover it can avoid over-damping performance. Experiment results obtained from a 200-V, 20-kW laboratory system verify the effectiveness of the active filter equipped with automatic gain adjustment.
引用
收藏
页码:438 / 447
页数:10
相关论文
共 12 条
[1]   Control strategy and site selection of a shunt active filter for damping of harmonic propagation in power distribution systems [J].
Akagi, H .
IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (01) :354-363
[2]   A shunt active filter based on voltage detection for harmonic termination of a radial power distribution line [J].
Akagi, H ;
Fujita, H ;
Wada, K .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1999, 35 (03) :638-645
[3]   An efficient approach for reducing harmonic voltage distortion in distribution systems with active power line conditioners [J].
Chang, TT ;
Chang, HC .
IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (03) :990-995
[4]   Minimizing harmonic voltage distortion with multiple current-constrained active power line conditioners [J].
Chang, WK ;
Grady, WM .
IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (02) :837-843
[5]   DEAD BEAT MICROPROCESSOR CONTROL OF PWM INVERTER FOR SINUSOIDAL OUTPUT WAVE-FORM SYNTHESIS [J].
GOKHALE, KP ;
KAWAMURA, A ;
HOFT, RG .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1987, 23 (05) :901-910
[6]  
JINTAKOSONWIT P, 2000, IEEE T POWER ELECTR, V147, P132
[7]   Robust dead-beat current control for PWM rectifiers and active filters [J].
Malesani, L ;
Mattavelli, P ;
Buso, S .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1999, 35 (03) :613-620
[8]  
Oku K., 1994, Transactions of the Institute of Electrical Engineers of Japan, Part B, V114-B, P234
[9]   A robust digital current control method for active power filters [J].
Sedighy, M ;
Dewan, SB ;
Dawson, FP .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2000, 36 (04) :1158-1164
[10]  
Susaki Y., 2000, Transactions of the Institute of Electrical Engineers of Japan, Part B, V120-B, P746