摘要
BACKGROUND. Pseudomonas aeruginosa has been increasingly recognized for its ability to cause significant hospital-associated outbreaks, particularly since the emergence of multidrug-resistant strains. Biofilm formation allows the pathogen to persist in environmental reservoirs. Thus, multiple hospital room design elements, including sink placement and design, can impact nosocomial transmission of P. aeruginosa and other pathogens. METHODS. From December 2004 through March 2006, 36 patients exposed to the intensive care unit or transplant units of a tertiary care hospital were infected with a multidrug-resistant strain of P. aeruginosa. All phenotypically similar isolates were examined for genetic relatedness by means of pulsed-field gel electrophoresis. Clinical characteristics of the affected patients were collected, and a detailed epidemiological and environmental investigation of potential sources was carried out. RESULTS. Seventeen of the infected patients died within 3 months; for 12 (71%) of these patients, infection with the outbreak organism contributed to or directly caused death. The source of the outbreak was traced to hand hygiene sink drains, where biofilms containing viable organisms were found. Testing by use of a commercial fluorescent marker demonstrated that when the sink was used for handwashing, drain contents splashed at least 1 meter from the sink. Various attempts were made to disinfect the drains, but it was only when the sinks were renovated to prevent splashing onto surrounding areas that the outbreak was terminated. CONCLUSION. This report highlights the importance of biofilms and of sink and patient room design in the propagation of an outbreak and suggests some strategies to reduce the risks associated with hospital sinks.
引用
收藏
页码:25 / 33
页数:9
相关论文
共 28 条
[1]
*AM I ARCH, 2006, 2006 GUID DES CONSTR, P50
[2]
Pseudomonas aeruginosa and Pseudomonas putida outbreak associated with contaminated water outlets in an oncohaematology paediatric unit [J].
Aumeran, C. ;
Paillard, C. ;
Robin, F. ;
Kanold, J. ;
Baud, O. ;
Bonnet, R. ;
Souweine, B. ;
Traore, O. .
JOURNAL OF HOSPITAL INFECTION, 2007, 65 (01) :47-53
[3]
Pseudomonas aeruginosa outbreak in a neonatal intensive care unit: A possible link to contaminated hand lotion [J].
Becks, VE ;
Lorenzoni, NM .
AMERICAN JOURNAL OF INFECTION CONTROL, 1995, 23 (06) :396-398
[4]
Outbreak of severe Pseudomonas aeruginosa infections caused by a contaminated drain in a whirlpool bathtub [J].
Berrouane, YF ;
McNutt, LA ;
Buschelman, BJ ;
Rhomberg, PR ;
Sanford, MD ;
Hollis, RJ ;
Pfaller, MA ;
Herwaldt, LA .
CLINICAL INFECTIOUS DISEASES, 2000, 31 (06) :1331-1337
[5]
Multi-resistant Pseudomonas aeruginosa outbreak associated with contaminated tap water in a neurosurgery intensive care unit [J].
Bert, F ;
Maubec, E ;
Bruneau, B ;
Berry, P ;
Lambert-Zechovsky, N .
JOURNAL OF HOSPITAL INFECTION, 1998, 39 (01) :53-62
[6]
Transmission pathways of Pseudomonas aeruginosa in intensive care units:: Don't go near the water [J].
Bonten, MJM ;
Weinstein, RA .
CRITICAL CARE MEDICINE, 2002, 30 (10) :2384-2385
[7]
Comparative evaluation of biofilm disinfectant efficacy tests [J].
Buckingham-Meyer, Kelli ;
Goeres, Darla M. ;
Hamilton, Martin A. .
JOURNAL OF MICROBIOLOGICAL METHODS, 2007, 70 (02) :236-244
[8]
An outbreak of multidrug-resistant Pseudomonas aeruginosa associated with increased risk of patient death in an intensive care unit [J].
Bukholm, G ;
Tannæs, T ;
Kjelsberg, ABB ;
Smith-Erichsen, N .
INFECTION CONTROL AND HOSPITAL EPIDEMIOLOGY, 2002, 23 (08) :441-446
[9]
CLARK JA, PLUMBING ENG PLUMBIN
[10]
Outbreak of severe Pseudomonas aeruginosa respiratory infections due to contaminated nebulizers [J].
Cobben, NAM ;
Drent, M ;
Jonkers, M ;
Wouters, EFM ;
Vaneechoutte, M ;
Stobberingh, EE .
JOURNAL OF HOSPITAL INFECTION, 1996, 33 (01) :63-70