Fire-induced smoke control via hybrid ventilation in a huge transit terminal subway station

被引:80
作者
Gao, Ran [1 ]
Li, Angui [1 ]
Hao, Xinpeng [1 ]
Lei, Wenjun [1 ]
Zhao, Yujiao [1 ]
Deng, Baoshun [2 ]
机构
[1] Xian Univ Architecture & Technol, Sch Environm & Municipal Engn, Xian 710055, Shaanxi, Peoples R China
[2] China Railway First Survey & Design Inst Grp Ltd, Xian 710043, Shaanxi, Peoples R China
关键词
Subway station; Plume; Smoke; Dispersion; Fire; FDS; Hybrid ventilation; ATRIUM; SIMULATION;
D O I
10.1016/j.enbuild.2011.11.018
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Hybrid ventilation is the building ventilation system that integrates natural and mechanical ventilation components to create a high efficiency and healthy ventilation system for a building. Here, hybrid ventilation is used to control fire-induced smoke in a huge transit terminal subway station. Four different grid systems are compared, and the sensitivities of these gird systems are analyzed. The effect of hybrid ventilation on carbon monoxide (CO) concentration reduction and its suppression effect on horizontal dispersion of smoke are also analyzed. Heat release rate, smoke temperature in the vertical direction, smoke layer height and CO concentration are validated with previous experimental data, and good agreement is achieved. Preliminary results show that the average CO concentration in the hall decreases significantly with increasing roof window size and air change rate (ACH). However, little CO concentration difference in the atrium can be observed. Comparing with the conventional mechanical ventilation, hybrid ventilation can inhibit the dispersion of smoke more effectively. The CO concentration in the subway station in the horizontal direction is significantly lower than that with conventional mechanical ventilation. It suggests hybrid ventilation by setting roof window in the ceiling of the atrium with size of 3 m x 3 m or larger can be an effective method to exhaust fire-induced smoke. (c) 2011 Elsevier B.V. All rights reserved.
引用
收藏
页码:280 / 289
页数:10
相关论文
共 37 条
[11]   Critical wind velocity for arresting upwind gas and smoke dispersion induced by near-wall fire in a road tunnel [J].
Hu, L. H. ;
Peng, W. ;
Huo, R. .
JOURNAL OF HAZARDOUS MATERIALS, 2008, 150 (01) :68-75
[12]  
Hua L.H., 2008, EXPT THERMAL FLUID S, V32, P1468
[13]  
Huo R., 2001, FIRE SCI TECHNOLOGY, V4, P3
[14]  
Joubert Patrice, NUMERICAL EXERCISE T
[15]  
Kevin J. Lomas, 2007, ENERG BUILDINGS, V39, P32
[16]   Performance prediction of a hybrid ventilation system in an apartment house [J].
Kim, Moo-Hyun ;
Hwang, Ji-Hyeon .
ENERGY AND BUILDINGS, 2009, 41 (06) :579-586
[17]   Resilience of naturally ventilated buildings to climate change: Advanced natural ventilation and hospital wards [J].
Lomas, Kevin John ;
Ji, Yingchun .
ENERGY AND BUILDINGS, 2009, 41 (06) :629-653
[18]  
MCGRATTAN K, 2006, NIST SPECIAL PUBLICA, V1018
[19]  
McGrattan K.B., 2006, NIST Special Publication, V1019
[20]  
Park W.H., 2006, Tunnelling and Underground Space Technology, V21, P304, DOI DOI 10.1016/J.TUST.2005.12.160