Partial discharge diagnostics and electrical equipment insulation condition assessment

被引:271
作者
Stone, GC [1 ]
机构
[1] Iris Power Engn, Unit 2, Toronto, ON M9C 1B2, Canada
关键词
D O I
10.1109/TDEI.2005.1522184
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Partial discharge (PD) measurement has long been used as a test to evaluate different insulation system designs, and as a quality control test for new equipment. However, in the past 20 years, PD measurement has been widely applied to diagnose the condition of the electrical insulation in operating apparatus such as switchgear, transformers, cables, as well as motor and generator stator windings. Improvements in the capabilities as well the lower cost of sensors, electronics and memory is partly the reason for the increased popularity of PD diagnostics. Another reason has been the development of methods - including the use of ultrawide band detection - to improve the reliability of the PD measurement in the presence of noise. In addition, rapid progress is being made in automated pattern recognition techniques that also helps to suppress noise. This paper reviews the various PD measurement technologies that have been specifically developed to improve PD diagnostic methods, and outlines how they have been implemented for stators, cables, transformers and switchgear. Areas for further research are also presented.
引用
收藏
页码:891 / 904
页数:14
相关论文
共 50 条
[1]   On-line partial discharge detection in cables [J].
Ahmed, NH ;
Srinivas, NN .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1998, 5 (02) :181-188
[2]  
[Anonymous], ASTM PUBLICATION STP
[3]  
[Anonymous], DIELECTRIC PHENOMENA
[4]   Partial discharges - Their mechanism, detection and measurement [J].
Bartnikas, R .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2002, 9 (05) :763-808
[5]  
BARTNIKAS R, 1969, IEEE T IM, P341
[6]  
BEYER M, 1982, IEEE T PAS, V100, P3451
[7]   ELECTROMAGNETIC TECHNIQUES FOR FAULT AND PARTIAL DISCHARGE LOCATION IN GAS-INSULATED CABLES AND SUBSTATIONS [J].
BOGGS, SA .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (07) :1935-1941
[8]  
BROWN PM, 1996, IEE C MON COND ASS E
[9]   Use of a mixed-Weibull distribution for the identification of PD phenomena [J].
Cacciari, M ;
Contin, A ;
Montanari, GC .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1995, 2 (06) :1166-1179
[10]   Advanced PD inference in on-field measurements. Part I: Noise rejection [J].
Cavallini, A ;
Contin, A ;
Montanari, GC ;
Puletti, F .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2003, 10 (02) :216-224