A generic real-time computer simulation model for superconducting fault current limiters and its application in system protection studies

被引:53
作者
Langston, J [1 ]
Steurer, M [1 ]
Woodruff, S [1 ]
Baldwin, T [1 ]
Tang, J [1 ]
机构
[1] Florida State Univ, Ctr Adv Power Syst, Tallahassee, FL 32310 USA
关键词
power system protection; real time simulation; superconducting fault current limiters (SCFCL);
D O I
10.1109/TASC.2005.849459
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 [电气工程]; 0809 [电子科学与技术];
摘要
A model for the SCFCL suitable for use in real time computer simulation is presented. The model accounts for the highly nonlinear quench behavior of BSCCO and includes the thermal aspects of the transient phenomena when the SCFCL is activated. Implemented in the RTDS real-time simulation tool the model has been validated against published BSCCO characteristics. As an example for an application in protection system studies, the effect of an SCFCL on a utility type impedance relay has been investigated using a real time hardware-in-the-loop (RT-HIL) experiment. The test setup is described and initial results are presented. They illustrate the effect of how the relay misinterprets the dynamically changing SCFCL impedance as an apparently more distant fault location. It is expected that the new real-time SCFCL model will provide a valuable tool not only for further protection system studies but for a wide range of RT-HIL experiments of power systems.
引用
收藏
页码:2090 / 2093
页数:4
相关论文
共 6 条
[1]
Limitations of fault-current limiters for expansion of electrical distribution systems [J].
Das, JC .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1997, 33 (04) :1073-1082
[2]
The effects of a fast switching fault current limiter on distance protection [J].
Henry, S ;
Baldwin, T ;
Steurer, M .
PROCEEDINGS OF THE 35TH SOUTHEASTERN SYMPOSIUM ON SYSTEM THEORY, 2003, :264-268
[3]
Setting method of specific parameters of a superconducting fault current limiter considering the operation of power system protection -: Resistance-type and rectifier-type SFCLs in overhead transmission systems [J].
Kameda, H ;
Taniguchi, H .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 1999, 9 (02) :1355-1360
[4]
PAUL W, P CIGRE SESS 2000
[5]
STEURER M, 2004, P IEEE GEN M DENV CO
[6]
Fault-current limiter applications in medium- and high-voltage power distribution systems [J].