Comparison of a 2D axisymmetric CFD model of a natural draft wet cooling tower and a 1D model

被引:50
作者
Williamson, N. [1 ]
Behnia, M. [2 ]
Armfield, S. [1 ]
机构
[1] Univ Sydney, Sch Aerosp Mech & Mechatron Engn, Sydney, NSW 2006, Australia
[2] Univ Sydney, Dean Grad Studies, Sydney, NSW 2006, Australia
关键词
natural draft wet cooling tower;
D O I
10.1016/j.ijheatmasstransfer.2007.11.008
中图分类号
O414.1 [热力学];
学科分类号
摘要
The performance predictions of a simple one-dimensional [natural draft wet cooling tower (NDWCT) model and a two-dimensional axisymmetric numerical model are compared under a range of design parameters. The two-dimensional model has the ability to resolve radial non-uniformities across the tower which the one-dimensional model only computes as a bulk averaged value. The difference between the overall cooling range predicted by the two models is generally less than 2%, with no divergence in the agreement between the methods with respect to any design parameter. (C) 2007 Elsevier Ltd. All rights reserved.
引用
收藏
页码:2227 / 2236
页数:10
相关论文
共 29 条
[1]   CFD simulation of wet cooling towers [J].
Al-Waked, R ;
Behnia, M .
APPLIED THERMAL ENGINEERING, 2006, 26 (04) :382-395
[2]  
ALWAKED R, 2005, THESIS U NEW S WALES
[3]  
ASHRAE, 2000, ASHRAE SYST EQ HDB
[4]  
Baker DR, 1961, J HEAT TRANSFER, V83, P339, DOI [10.1115/1.3682276, DOI 10.1115/1.3682276]
[5]  
BELLAGAMBA B, 1988, P 6 IAHR COOL TOW WO
[6]   Analysis of heat, mass, and momentum transfer in the rain zone of counterflow cooling towers [J].
de Villiers, E ;
Kröger, DG .
JOURNAL OF ENGINEERING FOR GAS TURBINES AND POWER-TRANSACTIONS OF THE ASME, 1999, 121 (04) :751-755
[7]   A modified analysis of counter flow wet cooling towers [J].
ElDessouky, HTA ;
AlHaddad, A ;
AlJuwayhel, F .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1997, 119 (03) :617-626
[8]  
Feltzin AE, 1991, COOLING TOWER INSTIT, V12, P8
[9]  
FLUENT Inc, 2003, FLUENT US GUID
[10]  
FOURNIER Y, 2001, P 12 IARH S COOL TOW