On the bidirectional flow across an atrium ceiling vent

被引:17
作者
Chow, W. K. [1 ]
Li, J. [2 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Area Strength Fire Safety Engn, Res Ctr Fire Engn, Kowloon, Hong Kong, Peoples R China
[2] Beijing Univ Technol, Coll Architecture & Civil Engn, Beijing 100124, Peoples R China
关键词
Horizontal ceiling vent; Bidirectional flow; Pressure drop; Smoke exhaust; SMALL OPENINGS; BUOYANCY;
D O I
10.1016/j.buildenv.2011.06.018
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Sizing of horizontal ceiling vent in a tall atrium is usually based on vent flow models with unidirectional flow. This is only good for natural vents with large pressure differences between inside and outside. For low pressure differential across the horizontal ceiling vent as experienced in some atrium fires, bidirectional smoke flow rates were observed. The extraction rate through the vent would be reduced, giving poor performance of the smoke exhaust system. Bidirectional flow across a ceiling vent will be discussed in this paper. Models available in the literature will be briefly reviewed first. A new model was developed on studying effects of bidirectional flow across a horizontal vent on the smoke layer interface height. A critical pressure difference between inside and outside across the vent can be estimated on inducing bidirectional flows. The approach is illustrated with an example sizing calculation for a cubic atrium commonly found in Hong Kong. (C) 2011 Elsevier Ltd. All rights reserved.
引用
收藏
页码:2598 / 2602
页数:5
相关论文
共 24 条
[11]  
COOPER LY, 1993, 5252 NISTIR
[12]  
Cooper LY, 1989, CALCULATION FLOW HOR, DOI [10.6028/NIST.IR.89-4052, DOI 10.6028/NIST.IR.89-4052]
[13]  
EMMONS HW, 1995, SFPE HDB FIRE PROTEC
[14]   Combined Natural Convection and Forced Flow Through Small Openings in a Horizontal Partition, With Special Reference to Flows in Multicompartment Enclosures [J].
Epstein, M. ;
Kenton, M. A. .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1989, 111 (1-4) :980-987
[15]   BUOYANCY-DRIVEN EXCHANGE FLOW THROUGH SMALL OPENINGS IN HORIZONTAL PARTITIONS [J].
EPSTEIN, M .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1988, 110 (4A) :885-893
[16]   ENGINEERING RELATIONS FOR FIRE PLUMES [J].
HESKESTAD, G .
FIRE SAFETY JOURNAL, 1984, 7 (01) :25-32
[17]  
HESKESTAD G, 1991, P 3 INT S FIR SAF SC, P919
[18]  
LEE SHK, 1993, COMB I E STAT SECT C, P327
[19]  
Li J., 2002, J APPL FIRE SCI, V11, P229, DOI DOI 10.2190/RK04-K8TA-1J92-E0F0
[20]   On the operation time of horizontal ceiling vent in an atrium [J].
Li, YZ ;
Huo, R ;
Chow, WK .
JOURNAL OF FIRE SCIENCES, 2002, 20 (01) :37-51